Electrically bond boiler to ground in accordance with       
requirements of authority having jurisdiction.  Refer to:
• USA- National Electrical Code, ANSI/NFPA 70.
• Canada - Canadian Electrical Code, Part I, CSA C22.1: 
Safety Standard for Electrical Installations.
Electric Power Supply
Prior to making any line Voltage connections, turn OFf 
electrical power at fuse box.
1. 
Run separate 115 Volt circuit from  separate over 
current protection device in electrical service entrance 
panel.  This should be 15 ampere circuit. 
2. 
See
 
 
Figure 20, Page 31
  for diagram showing service 
switch junction box and power supply connection 
points.  
3. 
Locate service switch in vicinity of boiler. Verify it is 
turned OFF during service or maintenance.
• Connect black (hot) lead from power supply to black 
wire labeled L 120 VAC. 
• Connect white (neutral) lead from power supply to 
white wire labeled N 120 VAC.
• Connect green (ground) lead from power supply to 
green wire labeled G 120 VAC.
4. 
Run 14 gauge or heavier copper wire from boiler to 
grounded connection in service panel or properly driven 
and electrically grounded ground rod.
ELECTRICAL WIRING
Thermostat Installation
• Thermostat location has important effect on operation 
of boiler system.
• Follow instructions included with your thermostat.
• Locate thermostat about fi ve feet above fl oor on inside 
wall. 
• Mount directly on wall or on vertical mounted outlet 
box. 
• It should be sensing average room temperature.
Set heat anticipator (where applicable) at 0.7 amps. 
Connect 24 Volt thermostat leads to two(2) yellow wires 
located in junction box, located on outer jacket of boiler. 
See  Figure 20, Page 31  for junction box and thermostat 
fi eld wiring connections.
Things to Avoid when Locating Thermostats
DEAD SPOTS:
Corners and alcoves
Behind doors
COLD SPOTS:
HOT SPOTS:
Concealed pipes or ducts
Concealed pipes     
Fireplace
Stairwells - drafts
TV sets
Radios
Unheated rooms on
other side of wall
Lamps
Direct sunlight
Kitchens
Connect Circulator Pump Wiring
See  Figure 20, Page 31  for circulator pump fi eld wiring con-
nections. 
Supplied 5 foot wiring harness with fl exible metal conduit 
for connection from circulator pump to junction box. 
If two 120 Volt circulator wire terminals inside junction box 
are not used, leave two wire nuts to prevent short circuit.
WARNING
Electrical shock hazard.  Turn OFF electrical power 
supply at service panel before making electrical  
connections.  Failure to do so could result in death 
or serious injury.
!
  
NOTICE
Label all wires prior to disconnection when servicing 
controls. Wiring errors can cause improper and 
dangerous operation. Verify proper operation after 
servicing.