Important
1. 
In reset from lockout condition, all electrical meter  
readings at the gas control valve (24 vac) must be 
taken within trial for ignition period.
2. 
If any component does not function properly, make 
sure it is correctly installed and wired before replacing 
it.
3. 
Static electricity discharge can damage integrated 
boiler control (IBC).  Touch metal surface to discharge 
static electricity before touching IBC.
4. 
IBC cannot be repaired.  If it malfunctions it must be 
replaced.
5. 
Only trained service technicians should service IBC 
systems.  Following troubleshooting, check out system 
following sequence of operation for a normal light off 
sequence.
6. 
All controls are factory tested in the assembly process 
and a defective control is generally the least likely 
cause.  If you suspect you have a defective control, 
read through this section before you replace it. 
7. 
It is extremely unlikely that the two consecutive 
controls are defective.  If it seems to be happening, 
chances are that either there is nothing wrong with the 
control or it is being damaged by some other problem 
(an electrical short burning out a transformer, for 
example).
Initial Service Checks
1. 
Before troubleshooting:
A.  Make sure that circuit breaker is on or fuse is ok at 
electrical panel.
B.  Make sure that service switch is on.
C.  Make sure that gas is on at the gas meter, at all 
appropriate manual shutoff valves and at the gas 
control valve.
D.  Make sure that the thermostat is calling for heat.
E.  Check that wire connectors at the integrated boiler 
control and at the originating control are securely 
plugged in or connected.
F.  Check that hoses are securely  connected and are 
not plugged or damaged.
 TROUBLESHOOTING
2. 
Troubleshooting tools:
A.  Voltmeter to check 120 vac and 24 vac
B. Continuity tester.
C.  Inclined manometer or pressure gauge with 
0-3.0” Range (0.01” Scale) for measuring suction 
pressures at pressure switch.
D.  U-tube manometer or differential pressure gauge 
with 0-14” range (0.1” Scale) for measuring inlet 
and manifold gas pressures.
3. 
IBC Error Codes.
A.  IBC uses advanced diagnostic capability to assist in 
troubleshooting error conditions.  Table 10, Page 48  
shows error codes that may arise during fault 
condition. 
B.  State Conditions shown in 
 
Table 9, Page 40
  
provide 
suggestions for servicing these potential errors.
WARNING
Fire, explosion or shock hazard. Do not attempt to 
modify the physical or electrical characteristics of 
this boiler in any way. Failure to comply could result 
in death or serious injury.
!