Справочник Пользователя для Lennox International Inc. GWB8-187IE-2

Скачать
Страница из 32
14
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use 
any phone in your building.
• Immediately call your gas supplier from a 
neighbor’s phone.  Follow gas supplier’s 
instructions. 
• If you cannot reach your gas supplier, call the fi re 
department.
!
!
  
Table 5 - Gas Pressures
PRESSURE
GAS
NATURAL
PROPANE
MIN. SUPPLY
5" w.c.
11" w.c.
MAX. SUPPLY
13.5" w.c.
13.5" w.c.
MANIFOLD
3.5" w.c.
10" w.c.
Verify minimum pressure while boiler is operating.               
Verify maximum pressure when boiler is not operating
Connecting Gas Piping
Gas line enters boiler from right side. Flexible gas 
connectors must never breach any boiler openings.              
• Use piping materials and joining methods acceptable 
to authority having jurisdiction.  In absence of such 
requirements:
• USA - National Fuel gas Code, ANSI Z223.1/NFPA 54
• Canada - Natural Gas and Propane Installation Code, 
CAN/CSA B149.1
• All pipe compound must be resistant to liquefi ed 
petroleum gas.
• Install ground joint union in gas supply line between 
shut-off valve and boiler controls.
• Install sediment trap upstream of gas controls.
• Use two pipe wrenches when making connection to gas 
valve to keep it from turning.
• Install manual shut-off valve in vertical pipe about 5 feet 
(1.5m) above fl oor. See Figure 8.
• Tighten all joints securely. 
• Propane gas connections should only be made by 
licensed propane installer.
• Two-stage regulation should be used by propane 
installer.
• Propane gas piping should be check by propane installer. 
Check Gas Supply
Gas pipe must be correct size for length of run and for 
total BTU per hour input of all gas utilization equipment 
connected to it. See Table 6 & 7, Page 15 for proper size. 
Be sure your gas line complies with local codes and gas 
company requirements.
DANGER
Fire Hazard.  Do not use matches, candles, open 
fl ames, or other methods providing ignition source. 
Failure to comply will result in death or serious        
injury.
!
  
Check Gas Piping
Pressure test boiler and gas connection before placing 
boiler in operation.
• Pressure test over 1/2 psig (3.5 kPa).  Disconnect 
boiler and its individual gas shutoff valve from gas 
supply system.
• Pressure test at 1/2 psig (3.5 kPa) or less.  Isolate 
boiler from gas supply system by closing manual gas 
shutoff valve. See Figure 8.
• Locate leakage using gas detector, noncorrosive 
detection fl uid, or other leak detection method 
acceptable to authority having jurisdiction. 
• Correct leaks immediately and retest.
GAS SUPPLY PIPING
Figure 8  - Gas Piping At Boiler