Burners
Beginning of heating season visually check pilot and main 
burner fl ames.  See Figures 13, and 14.
Safety Relief Valve
Test safety relief valve for proper operation.  Refer to valve 
manufacturer’s instructions packaged with relief valve.
Expansion Tank (Non-diaphragm)
Tank may become waterlogged, or may receive excess 
of air. Frequent automatic opening of safety relief 
valve indicates water logging. High boiler temperature 
accompanied by unusually low radiation unit temperature 
(and “knocking”) indicates excess air in tank.
To correct:
1. 
Close valve between boiler and tank. Drain tank until 
empty. 
2. 
Check all tank plugs and fi ttings. Tighten as necessary. 
3. 
Open valve between boiler and tank. Water will rise to 
normal height in tank if you have automatic fi ll valve 
(otherwise, manually refi ll system).
Boiler Flue Passages
Recommend following checked annually by qualifi ed service 
agent. 
• fl ue passages 
• burner adjustment
• operation of controls
Before start of each season (or whenever system has been 
shut down for some time) recheck whole system for leaks 
and recheck boiler and vent pipe for leaks. Replace or patch 
any boiler seals that are faulty. Before start of each season
(or whenever system has been shut down for some time) 
recheck the whole system for leaks . . . and recheck the 
boiler and vent pipe for leaks. Replace or patch any boiler 
seals that are faulty.
Vent Pipe
Venting and piping should be checked at least monthly. If 
vent piping shows any sign of leaking, replace immediately. 
Water System
If system is to remain out of service during freezing 
weather, always drain it completely (water left in to freeze 
will crack pipes and/or boiler).   
Cleaning Your Boiler And Burners
Flue passages between sections should be examined yearly 
and cleaned if necessary. 
To clean: 
• Remove burners, pilot, and vent pipe.
• Remove top and front jacket panels. 
• Remove two screws attaching intermediate front panel 
to left and right side jacket panels. 
• Remove control panel. 
• Remove draft diverter and intermediate front panel.
• Carefully remove cerafelt gasket strips. 
• Clean passageways between sections with fl exible 
handle wire brush. Remove dirt from bottom of boiler 
and from between sections by vacuuming. 
• Verify all fl ame ports in burners are open and clear. 
Shake out or blow out all loose dirt in burners. 
• Reseal seams between adjacent sections as necessary 
with 400
°
 F RTV silicone sealant. 
• Reassemble all parts. 
• Verify tightness of pilot connections and condition of 
burner fl ames after reassembly. See Figures 13 and 14. 
• Verify vent pipe connections to chimney are secure and 
no obstructions are present. 
Blower 
Blower motor features permanently lubricated ball bearing 
construction. Lubrication is not required. 
Circulator Pump Isolation Valves
Operate isolation valves in circulator pump fl anges 
manually once or twice per year to prevent valves from 
becoming stuck in open position 
Rotate valves from open position to closed position and 
back to open position.
Low Water Cutoff(s)
Inspect fi eld sourced low water cutoffs annually or 
as recommended by low water cutoff manufacturer.  
Flush fl oat type low water cutoff(s) per manufacturer’s 
instructions.
Housekeeping
• Keep boiler area clear and free from combustible 
materials, gasoline and other fl ammable vapors and 
liquids.
• Keep boiler area clear of debris and other materials 
obstructing fl ow of combustion and ventilation air.
MAINTAINING YOUR BOILER