Справочник Пользователя для Rackmount Solutions VA 700

Скачать
Страница из 58
Table 7.  Minimum Requirements for E-Series UPS Installation
Term 
ID
Description
E61 (E41)
E101 (E81)
E203 (E153)
Min. 
Wire 
Gaug
(awg)
Term 
Torqu
e (in-
lbs)
Min. 
Wire 
Temp
. (°C)*
Min. 
Wire 
Gaug
(awg)
Term 
Torqu
e (in-
lbs)
Min. 
Wire 
Temp
. (°C)*
Min. 
Wire 
Gaug
(awg)
Term 
Torqu
e (in-
lbs)
Min. 
Wire 
Temp
(°C)*
GND
Chassis 
Ground
**
40
75
**
45
75
**
45
90
L1/N
Line 1
8
40
75
6
45
75
4
45
90
L2
Line 2
8
40
75
6
45
75
4
45
90
L3
Line 3
N/A
N/A
N/A
N/A
N/A
N/A
4
45
90
120A
120 V from 
Neutral
10
35
75
6
45
75
4
45
90
0
Neutral 
10
35
75
6
45
75
4
45
90
88B
208 V from 
120A
10
35
75
6
45
75
4
45
90
120B
120 V from 
Neutral
10
35
75
6
45
75
4
45
90
GND
Chassis 
Ground
opt
35
75
opt
45
75
opt
45
90
+
+240 VDC to -
N/A
N/A
N/A
4
45
75
4
45
75
-
Battery 
Common
N/A
N/A
N/A
4
45
75
4
45
75
GND
Chassis 
Ground
N/A
N/A
N/A
4
45
75
4
45
75
*  Use insulated copper wire rated 75 C minimum.
** Must be no smaller than wire connected to L1/N and L2 (for E61 and E101) or L1, L2, L3 (for E203).
GND L1/N L2 120
0
88B 120 GND
208
120
120
LINE
OUT-
X3
X4
X2
X1
Chloride Active and E-Series UPS User Manual
35
Fig. 23: Wiring Diagram for the E61