Chloride Active and E-Series UPS User Manual
Fig. 28:  Connection of an External Battery Cabinet to Type E101
Fig. 29: Connection of an External Battery cabinet to Type E203
WARNING: The connection of the external battery cabinet may only be done by qualified personnel 
in accordance with the applicable safety regulations.
CAUTION: For the electrical installation, the maximum load capacity of the connection cable has to be taken into 
account. 
Table 9.  Technical data of the connection cable
 E101
E203
Minimum permissible cable cross section
6 mm
2
, 8 AWG
4 AWG
Maximum permissible cable cross section
20 mm
2
, 4 AWG
4 AWG
Nominal operating voltage
240 VDC
240 VDC