 Reference, Installation, and Operations Manual
Section 6: Meter operation
3-9000-743 Rev S
June 2013
AGA8 compressibility calculations
 215
6.1.17
AGA8 compressibility calculations
The Mark III meter utilizes AGA8 compressibility calculation results for profile-effect correction 
(for JuniorSonic
TM
 meters) and flow-condition-to-base-condition of the volumetric flow rate.
The Mark III meter provides for five AGA8 method selections via the 
HCH_Method data point:
external (0) with results specified to the meter (via the 
SpecRhoMixFlowSpecZFlow
and 
SpecZBase data points)
internal via Gross Method 1 (1)
internal via Gross Method 2 (2)
internal via Detail Method (3)
None (4) (AGA8 calculations are not performed)
Refer to 
 for information on configuring the meter for AGA8 calculations via the 
Daniel MeterLink program.
6.2
Frequency, digital, and analog outputs
The Mark III meter provides two pairs of individually configurable frequency outputs (FO1A, 
FO1B, FO2A, and FO2B), four individually configurable digital outputs (DO1A, DO1B, DO2A, and 
DO2B), and an optional analog output (AO1 via the Option Board). The frequency and digital 
outputs are divided into two groups as follows:
Group 1:FO1A, FO1B, DO1A, DO1B
Group 2:FO2A, FO2B, DO2A, DO2B
The two members of a frequency output pair are referred to as channel “A” and the channel “B”.
Each group has a separate ground (i.e., Group1Gnd and Group2Gnd) thus allowing each output 
group to be connected to a different flow computer. Refer to 
 for further 
information on the hardware configuration options for these outputs.
The frequency, digital, and analog outputs are updated at the batch update period.
6.2.1
Frequency outputs
The following paragraphs describe the frequency output pair options in detail. Since each 
frequency output pair is individually configurable, the data point names are identical except for 
the pair identifier (‘1’ or ‘2’). For example, the frequency pair content data points are 
Freq1Content and Freq2Content. For brevity, they are identified as FreqXContent where X 
represents 
1 or 2.
Refer to 
 for information on configuring these outputs using the Daniel MeterLink 
Field Setup Wizard
. The associated configuration data points can also be configured via the 
Daniel MeterLink 
Edit/Compare Configuration
 screen.