 Reference, Installation, and Operations Manual
Section 6: Meter operation
3-9000-743 Rev S
June 2013
Digital outputs
 219
6.2.2
Digital outputs
The following paragraphs describe the digital output configuration options.
Refer to 
 for information on configuring these outputs using the Daniel MeterLink 
Field Setup Wizard
. The associated configuration data points can also be configured via the 
Daniel MeterLink 
Edit/Compare Configuration
 screen.
Digital output data content
The group 1 digital outputs are configured via the 
DO1AContent and DO1BContent data 
points to represent the Frequency 1 data validity (0) or the flow direction (2).
The group 2 digital outputs are configured via the 
DO2AContent and DO2BContent data 
points to represent the Frequency 2 data validity (1) or the flow direction (2).
Digital output data polarity
When a digital output represents frequency data validity, the normal polarity is for the signal to 
be:
a logic ‘high’ when the frequency is valid, and
a logic ‘low’ when the frequency is invalid.
When a digital output represents the flow direction, the normal polarity is for the signal to be:
a logic ‘high’ when the flow is in the forward direction, and
a logic ‘low’ when the flow is in the reverse direction.
The 
DO1AIsInvPolarityDO1BIsInvPolarityDO2AIsInvPolarity, and DO2BIsInvPolarity 
data points are used to configure the digital output polarities as follows:
FALSE - normal polarity (default setting), or
TRUE - inverted polarity
Digital output value data points
The value of each digital output is readable via a data point (
DO1ADO1BDO2A, and DO2B).