Справочник Пользователя для Emerson Process Management 3420

Скачать
Страница из 398
 250
Alarm log
Section 6: Meter operation
 Reference, Installation, and Operations Manual
June 2013
3-9000-743 Rev S
6.6.4
Alarm log
The Mark III meter monitors several data points with respect to each point’s alarm limit(s). Non-
boolean data points can have low and high alarm limits. Boolean data points only have a single 
alarm limit (i.e., either TRUE or FALSE). There are two statuses associated with alarms: set and 
cleared. An alarm is set when the data point is at or exceeds its alarm limit. An alarm is cleared 
when the data point is within its alarm limit(s).
The Mark III meter stores an alarm log record whenever any monitored data point’s alarm status 
(cleared or set) changes. The alarm log record indicates the data point, date and time, alarm 
status, corresponding alarm limit, and data point value.
The meter can store up to 3000 alarm records. The user can select whether old, unread records 
can be overwritten by new records when the log becomes full via the data point 
DoOverwriteUnreadAlarmLog. This point can be modified using the Daniel MeterLink Tools - 
Edit/Compare Configuration
 screen. The default is to overwrite old, unread records. Refer to 
 for information on reading records and marking records as read. The data point 
IsAlarmLogFull indicates whether or not the alarm log is full and cannot overwrite old, unread 
records.
The user-settable data points 
AlarmTurnOffHysterisisCount and AlarmTurnOffHysterisis-
TimeSpan are used to prevent very repetitive alarms from filling up the alarm log. When an 
alarm is set 
AlarmTurnOffHysterisisCount times within AlarmTurnOffHysteresisTimeSpan 
seconds, then the alarm is suppressed until the alarm frequency drops below the specified rate 
(counts per time span) at which point the next alarm clearing “unsuppresses” the alarm. The 
alarm log records indicate when an alarm suppression is started and ended. The default values 
are 8 occurrences in 240 seconds.
The data points monitored for the alarm log are as shown in 
 and 
 below. 
Note that the alarm limits are themselves data points. The user-settable alarm limits are listed 
by data point name. Non-settable alarm limits are listed by data point value.
Table 6-21  Alarm log non-boolean data points monitored
Data Point
Low Alarm Limit
High Alarm Limit
GainAUp, GainADn,
GainBUp, GainBDn,
GainCUp, GainCDn,
GainDUp, GainDDn
GainLowLmt
GainHighLmt
AvgSndVel
AvgSoundVelLoLmt
AvgSoundVelHiLmt
AGA8BaseCalcStatus
1
AGA8FlowCalcStatus
1
SpecFlowPressure
LowPressureAlarm
HighPressureAlarm
SpecFlowTemperature
LowTemperatureAlarm
HighTemperatureAlarm
LiveFlowPressure
LowPressureAlarm
HighPressureAlarm
LiveFlowTemperature
LowTemperatureAlarm
HighTemperatureAlarm