8 - 22
MELSEC-A
8   OTHER FUNCTIONS
(b)   When using the dedicated command with the QCPU (Q mode)
/ QnACPU
Registration execution
Write "0" in                 to 
register (default value is "4")
Set EEPROM function 
request (RYn7)
Reset EEPROM function 
request (RYn7)
R2 1C0
H
8.9 Controlling the RS-232-C signal
The status of the RS-232-C interface signals stored in the R2 buffer memory can be
read and the output controlled.
This is carried out with the remote input/remote output (RX/RY).
8.9.1 Correspondence of RS-232-C control signal and remote input/output signal
The correspondence of the RS-232-C interface control signals and the remote
input/output signals (RX/RY) is shown below.
Remote input/output
signal
RS-232-C control
signal
Details
RXn9
CS (CTS) signal
RXnA
DR (DSR) signal
Input signal
RXnB
CD signal
The ON/OFF state of the input control signal
is reflected on the corresponding remote input
signal (RXn9 to RXnB).
RYn9
RS (RTS) signal
Output signal
RYnA
ER (DTR) signal
The ON/OFF state of the remote output signal
is reflected on the corresponding control
signal output.
The area between the RS-232-C control signal and input/output signal (RX/RY) is
updated every 100ms.
Refer to section 3.3 for details on each RS-232-C signal.