3   SPECIFICATIONS
3.6 Input/output signals for master module
The input/output signals (RX/RY) for the R2 master module are explained in this
section.
3.6.1 List of input/output signals
A list of the R2 input/output signals is shown below.
Signal direction Master module   R2
Signal direction Master module   R2
Device No. (input)
Signal name
Device No. (output)
Signal name
RXn0
Transmission normal complete
RYn0
Transmission request
RXn1
Transmission error complete
RYn1
Transmission cancel request
RXn2
Reception normal read request
RYn2
Reception read complete
RXn3
Reception error read request
RYn3
Forced reception complete request
RXn4
Initialization normal complete
RYn4
Initialization request
RXn5
Initialization error complete
RYn5
Use prohibited
RXn6
OS reception area clear complete
RYn6
OS reception area clear request
RXn7
EEPROM function normal complete
RYn7
EEPROM function request
RXn8
EEPROM function error complete
RYn8
Use prohibited
RXn9
CS (CTS) signal
RYn9
RS (RST) signal  *
1
RXnA
DR (DSR) signal
RYnA
Signal setting
ER (DTR) signal  *
2
RXnB
Signal status
CD signal
RYnB
Use prohibited
RXnC to RXnD
General-purpose external input signal
RYnC to RYnD
General-purpose external output signal
RXnE to RX(n+1)8
Use prohibited
RYnE to RY(n+1)8
Use prohibited
RX(n+1)9
Initial data read complete
RY(n+1)9
Initial data read request
RX(n+1)A
Error state
RY(n+1)A
Error reset request
RX(n+1)B
Remote station ready
RX(n+1)C to
RX(n+1)D
Use prohibited
RY(n+1)B to RY(n+1)D Use prohibited
RX(n+1)E
Intelligent device station access complete
RY(n+1)E
Intelligent device station access request
RX(n+1)F
Use prohibited
RY(n+1)F
Use prohibited
n: Address assigned to master module with station No. setting.
*1  The RS signal setting is valid when the "RS signal status designation (
R 2
 101
H
)" is set to "Follow
RYn9 ON/OFF (1)". (Refer to section 8.9.)
*2
The ER signal setting is invalid when the "Flow control designation (
R 2
 100
H
)" is set to "Carry out
flow control. (DTR/DSR/ (ER/DR) control) (1)".
Important
Do not designate the RXn0 to RXn8, RXnE to RX(n+1)F, RYn0 to RYn9, RYnB, or RYnE to
RY (N+1)F signals to the following functions.
Monitor target RX/RY for monitor transmission function
Reference RX/RY for registration frame RX/RY/RW reference special character.
Do not output (turn ON) the usage-prohibited signals.
If an output is carried out to a usage-prohibited signal, the programmable controller system
could malfunction.