Circuit Mapping and Cross-Zoning
Input-to-Output Circuit Mapping and Cross-Zone Operation
106
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
Example 4: A dual hazard, cross-zoned application using four input zones and two releasing output 
circuits.  Input Zones 1 and 2 are cross-zoned to activate Output Circuit 2, which is programmed as 
RELEASE 1.  Input Zones 3 and 4 are cross-zoned to activate Output Circuit 3, which is 
programmed as a RELEASE 2.
Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.
Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.
Output Circuit 3 is programmed as Release Circuit 2 using the OUTPUT CIRCUITS menus
Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.
Any of smoke detector Input Zones 1 through 4 will directly activate Output Circuit 1 (Alarm 
NAC) but not Output Circuits 2, 3 or 4. 
Smoke detector Input Zones 1 and 2 are cross-zoned (both must be in alarm) to activate 
Output Circuit 2 (Release 1) but not Output Circuits 3 or 4.
Smoke detector Input Zones 3 and 4 are cross-zoned (both must be in alarm) to activate 
Output Circuit 3 (Release 2) but not Output Circuits 2 or 4.
                ZONE 1 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
               OUTPUT MAP ZONE 1
1=ALARM NAC                         YES
2=RELEASE 1                          YES
3=RELEASE 2                          NO
               OUTPUT MAP ZONE 1
1=SUPV BELL NAC                 N/A
           REL 1 CROSS GROUP 1
1=ZONE 1                                  YES
2=ZONE 2                                  YES
3=ZONE 3                                  NO
               OUTPUT MAP ZONE 2
1=SUPV BELL NAC                 N/A
                ZONE 2 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
               OUTPUT MAP ZONE 2
1=ALARM NAC                         YES
2=RELEASE 1                          YES
3=RELEASE 2                          NO
                ZONE 3 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
                ZONE 4 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
               OUTPUT MAP ZONE 3
1=ALARM NAC                         YES
2=RELEASE 1                          NO
3=RELEASE 2                          YES
               OUTPUT MAP ZONE 3
1=SUPV BELL NAC                 N/A
               OUTPUT MAP ZONE 4
1=SUPV BELL NAC                 N/A
               OUTPUT MAP ZONE 4
1=ALARM NAC                         YES
2=RELEASE 1                          NO
3=RELEASE 2                          YES
           REL 2 CROSS GROUP 1
1=ZONE 1                                  NO
2=ZONE 2                                  NO
3=ZONE 3                                  YES
           REL 2 CROSS GROUP 1
1=ZONE 4                                  YES
2=ZONE 5                                  NO
3=ZONE 6                                  NO