Strata CTX670 Installation
Install AC Power Components
4-24
Strata CTX I&M        06/04
Cabinet AC Power Considerations
The CTX670 power supply works with either 120VAC, 208VAC or 240VAC. CTX670 only 
requires 120VAC (up to three cabinets if one AC cord is allowed or five cabinets if two AC cords 
are allowed – see below). 
If the system has more then five cabinets, 208VAC or 240AVC is required for the primary AC 
power source. 208VAC or 240VAC can always be optionally used for systems with five or less 
cabinets for future growth or, if the electrical code requires.
To determine AC power requirements, you need to check local electrical code requirements for 
120VAC, 208VAC or 240VAC primary power. Some electrical codes stipulate that:
208VAC or 240VAC is required for telephones systems
Only one electrical cord can connect to the telephone system. 
Only two electrical cords can connect to the telephone system.
No electrical cord can connect to the telephone system – must use conduit wiring installed by a 
certified electrician (example: when system is floor mounted).
Cabinet AC Power Component Requirements for Wall Mounted 
Systems
 show the cabinet parts required to distribute AC power for various 
configurations of the CTX670 cabinets. 
 show how to install these parts.
Important!
The plugs and wall receptacles required by the local electrical code might differ for 
208VAC and 240VAC. Thus in some areas of the U.S., the plug used on the Toshiba 
240VAC power strip and 240VAC power supply cord (NEMA code 6-20P) can not 
be used for 208VAC installations. In this case, when using 208VAC, the AC plugs on 
the BPSB240 power strip cord that connects directly to the 208VAC wall outlet must 
be changed by a certified electrician per the local electrical code.
Table 4-2
Wall Mount Cabinet Power Component Requirements for 120VAC Primary Power 
Local Electrical Code
Cabinets
1
2
3
4
5
6
7
Allows only one 120VAC 
power cord from system
0 RPSB2
1 RPSB2
1 RPSB2
N/A 
N/A
N/A
N/A
Allows two 120VAC power 
cords from system
0 RPSB2
0 RPSB2
1 RPSB2
1 RPSB2
2 RPSB2
N/A
N/A
One dedicated, isolated, 20 amp. AC circuit breaker with dual outlets is required. 
N/A= If the system contains more than three cabinets and if the local code allows only one AC cord, the system requires a 
BCCB120 conduit box wired by a certified electrician when using 120VAC as primary power. Otherwise, 208VAC or 
240VAC should be used as the primary power source (see cabinet power options listed below).
Table 4-3
Wall Mount Cabinet Power Component Requirements for 208VAC or 
240VAC Primary Power
Local 
Electrical 
Code
Cabinets
1
2
3
4
5
6
7
Allows One 
AC power 
cord from 
system
1 BACL240
1 BPSB240
2 BACL240
1 BPSB240
3 BACL240
2 BPSB240
4 BACL240
2 BPSB240
5 BACL240
3 BPSB240
6 BACL240
3 BPSB240
7 BACL240