SPX Cooling Technologies 800 用户手册

下载
页码 28
     
11
Freezing Weather Operation
During periods of low ambient air temperatures, °F to 0°F (°C to 
°C) or below, it is advisable to maintain the cold water temperature 
at or above 0°F (1°C) to retard the formation of ice and to assist 
in its control. The methods used in Minimizing Tower Energy Use, 
described  on  page  1  are  those  which  the  operator  would  use  to 
maintain water temperature at or above 0°F (1°C).  
In combinations of low ambient air temperatures and reduced loads, fan 
speed manipulation may not be sufficient to maintain an acceptable water 
temperature. Even with fans off, the natural movement of air through the 
tower may be enough to continue reducing the water temperature. When 
that happens, it will become necessary to open the bypass valve, if so 
equipped, and allow total circulation to flow directly into the cold water 
basin until such time as the basin water inventory rises to a temperature 
level sufficiently high to preclude frequent changeovers from normal flow 
to bypass flow. That temperature level might be 85°F to 90°F (29°C to 
32°C), but should be determined by operator experimentation.
Deicing
The formation of ice on towers operating in freezing weather cannot be 
completely prevented, but can be acceptably controlled. Ice will form on 
the relatively dry parts of the tower that are in contact with the incoming 
air. Primarily, this includes the columns, structural framing, and fill at the air 
inlets. Ice forming characteristics on any given tower will vary, depending 
on velocity and direction of wind, circulating water rate and heat load. 
The Class 800 tower is designed with few structural components in the 
falling water zone, which prevents damage due to falling ice. However, 
structural damage can still result from excessive buildup of ice attached 
to the fill.
A regularly programmed inspection (one walk around the tower per shift) 
during cold weather operation is the best way to determine if ice buildup 
on the fill is occurring. If ice is observed and determined to be acceptable, 
maintain full (total) design flow over the tower. Excessive ice formation 
may be controlled by regulating air and water flow through the tower by 
one or more of the following procedures:
• Shut  the  fan  down.  This  reduces  the  cooling  rate  to  a  minimum  and 
increases the quantity of warm water at the air inlet to a maximum. Ex-
cept for extreme cold conditions or extended freezing conditions, this 
procedure will normally control ice formation. If the tower has two-speed 
motors, operate the fan at half speed forward. This also reduces the 
cooling rate and increases the quantity of warm water at the air inlet.
 
 Note