1.  The electronic thermostat controls the 24-volt circuit to the ignition control.  
When the thermostat contacts close, a 24-volt circuit is completed from the 
transformer through the thermostat relay to the ignition control module to 
initiate the ignition sequence. 
2.  On  flue damper models, the damper reaches then full open position, the 
end switches in the damper close, completing the 24-volt circuit to the 
ignition module. 
3.  The ignition control sends 24-volt power to the pilot valve “PV” terminals on 
the gas valve allowing pilot gas to flow to the pilot.  The ignition control also 
simultaneously sends high voltage low current electricity through the 
electrode wire to the pilot electrode causing sparks at the pilot electrode to 
ignite the pilot gas.  If the pilot fails to ignite within 90 seconds, the ignition 
control stops the pilot gas and sparking for 15 seconds to allow gas to 
dissipate.  The ignition control will then attempt 2 (two) more ignition trials 
as stated above.  If the pilot does not ignite after 3 trials, the ignition control 
will then go into “lockout mode”, and the ignition system will remain shut 
down until the control is reset by interrupting power to the ignition module. 
4.  When the pilot gas ignites, the flame is sensed by the electrode or a flame 
sensing rod.  The flame sensing signal received by the ignition control 
causes the sparking to stop and the main gas valve to open.  The main 
burners ignite from the pilot flame.  The pilot flame is continually monitored 
by the flame sensing circuit.  If for any reason, the pilot flame is not sensed 
by the electrode or flame sensing rod, the main gas valve closes, the spark 
electrode is reenergized, and the ignition trial period is reestablished.  The 
same sequence occurs during a power or gas supply interruption. 
5.  The main burners continue to operate until the water temperature in the 
tank increases enough to cause the thermostat contacts to open.  When 
the thermostat contacts open the 24-volt power is interrupted to the ignition 
control module and the gas valve closes.  The flue damper (on “D” models) 
closes. 
6.  If for some reason thermostat contacts fail to open, then the high 
temperature limit (ECO) contacts in the thermostat sensor open and 
interrupts power to the pilot valve causing the pilot to extinguish.  The 
ignition module senses the pilot outage and attempts to relight the pilot by 
reestablishing the sparking at the electrode as stated in paragraph 3 
above.  Since the pilot valve circuit is open, the pilot will not ignite and the 
system will go into “lockout mode” after 3 ignition trials.  In the “lockout 
mode”, the ignition system will remain shutdown until the control is reset by 
interrupting power to the ignition module.  The ECO will not reset to close 
the contacts until the tank water temperature drops to between 100°F 
(38°C) and 160°F (71°C).  If the ECO contacts open, the cause for the high 
water temperature should be determined before resetting the ignition 
system. 
 