InRow SC Operation
Mechanical
Electrical Hazard: Turn off the cooling unit and disconnect all power sources. Perform Lockout/
Tagout procedures before performing any electrical or mechanical service. Wear appropriate 
personal protective equipment when checking hazardous voltages.
‰ Check the fans. All components should be moving freely, with no signs of binding or damage. 
‰ Verify that the condensate line is flowing freely. 
Electrical
Electrical Hazard: Turn off the cooling unit and disconnect all power sources. Perform Lockout/
Tagout procedures before performing any electrical or mechanical service. Wear appropriate 
personal protective equipment when checking hazardous voltages.
Electrical Hazard: A Leakage Current Detector and Interrupter (LCDI) plug detects if there is 
damage to the power cord that could cause arcing between wires, resulting in a fire. The LCDI shuts 
off power if the power cord is damaged.The cooling unit should be in Standby mode before testing 
the LCDI plug.
‰ Inspect the power cord for damage. The power cord for the ACSC100 (60Hz) has a test button on the cord 
to test the LCDI plug.