HDV Series Direct Vent Gas Fireplace
4
56D3048
VeNtING INStAllAtIoN 
Note: If an offset is needed to avoid obstructions, you 
must support the vent pipe every three (3) feet. Use wall 
straps for this purpose. See Figure 33, page 6. Whenever 
possible, use 45° elbows instead  of 90° elbows. The 45° 
elbow offers less restriction to the flow of the flue gases 
and intake air.
5.  Place the flashing over the pipe section(s) extending 
through the roof. Secure the base of the flashing to 
the roof and framing with roofing nails. Be sure roofing 
material overlaps the top edge of the flashing. There 
must be a 1" clearance from the vent pipe to combus-
tible materials.  
6.  Continue to add pipe sections until the height of the 
vent cap meets the minimum requirements below.
Note:  You  must  increase  vent  height  for  steep  roof 
pitches. Nearby trees, adjoining roof lines, steep pitched 
roofs, and other similar factors may cause poor draft or 
down-drafting  in  high  winds.  Increasing  the  vent  height 
may solve this problem.
FP1969
firestop w room above
Figure 33 - 
If area above is a room, install firestop above framed 
hole as shown 
Firestop 
Nails
FP1969
10
56O"
10
56O"
FP1970
firestop no room
956O
"
956O
"
Figure 34 - 
If area above is not a room, install firestop below 
framed hole as shown 
Nails
Firestop 
FP1970
4 x 6B\,
Venting
5 x 8
Venting
Note: If the vent pipe passes through any occupied areas 
above the first floor, including storage spaces and closets, 
you must enclose pipe. You may frame and sheetrock the 
enclosure with standard construction material. Make sure 
to meet the minimum allowable clearances to combustibles. 
Do  not  fill  any  of  the  required  clearance  spaces  with 
insulation.  
2 ft. 
Min.
2 ft. Min.
X
12
H*
FP1971
Min chimney clearance
Termination 
Vent
Storm 
Collar
Flashing
Lowest 
Discharge 
Opening
Concentric 
Vent Pipe
1” Minimum Clearance to 
Combustibles
FP1971
Horizontal Overhang
Figure 35 - 
Minimum Chimney Clearance
 
 
 
Roof Pitch 
Feet 
Meters
  Flat to 7/1 
1.0 
.3
  Over 7/1 to 8/1 
1.5 
.46
  Over 8/1 to 9/1 
.0 
.61
  Over 9/1 to 10/1 
.5 
.76
  Over 10/1 to 11/1 
3.5 
.99
  Over 11/1 to 1/1 
4.0 
1.
  Over 1/1 to 14/1 
1.5
*H - Minimum height from roof to 
lowest discharge opening of vent