M400BFC Balanced Flue Heat-Circulating Fireplace
87D1505
WARNING:  Hearth extension must be installed in 
accordance with Figure 23 and must not cover the 
bottom front opening of the circulating model.
Alternate noncombustible materials may be used pro-
viding the (total) thermal resistance (Rt value) of the al-
ternate material employed is greater than or equal to R 
=  1.09 Thermal resistance (R) or thermal conductivity 
(K), may be obtained from manufacturer of the material.  
Factors are related by the formula K = 1/R. (Fig. 24)
T = given thickness
R = thermal resistance for a given thickness (T)
K = thermal conductivity
Noncombustible material with a lower R value may 
be used, provided thickness of material is sufficiently 
greater to maintain an equivalent (total) thermal resis-
tance (Rt).
COMMON MATERIALS AND FACTORS
MATERIAL
K*
R
MINIMUM
THICKNESS
EH2416 
Common Brick
0.458
5.0
1.09    0.50 in.**        
0.10    5.46 in.**       
(MHSC)
   R Value is for 1/2 inch.
 * Units of K = BTU/SQ FT/HR/˚F/IN
** Thickness of Listed Material
FP533ADD
Addendum
6/1/99   djt
8/4/99 changed .2 to .1
one inch to 1/2 inch  djt
FP533ADD
Fig. 22  Hearth extension material factors.
Example of Determining Hearth Extension 
Equivalents
To determine the thickness required for any new mate-
rial:
NEW 
  K of new material (per inch) 
 
thickness
required 
=  ---------------------------------------  X  of listed
thickness 
  K of listed material (per inch)   
material
Example for Common Brick
T (new) = 5.0/0.458 x 0.50 in. = 5.46 in. (new required 
thickness).
FP550
BR/BC - SEALING
DETAILS
9/29/97
Wall Covering
Noncombustible 
Decorative Fac-
ing
Seal all cracks 
between fireplace 
surround and wall 
materials with non-
combustible material.
Noncombus-
tible Decorative 
Covering
Hearth Exten-
sion Insulation
2 x 4” Header 
- Do not notch at 
standoffs
Seal crack between 
fireplace and hearth 
extension with noncom-
bustible material
Safety Strips - 
Must be overlapped 1/2” 
minimum
Side View
FP550
Fig. 23  Sealing gaps.
KT108b
BFC
Correct door position
8/23/00   djt
Correct
Wrong
Fig. 28  Correct door position.
KT108b
Glass Door Operation
The M400BFC is intended for use only with the doors 
fully closed. (Fig. 28)