INSTALLATION
EXTERIOR FLUE TERMINATION LOCATIONS
Minimum clearances required for balanced fl ue terminals or 
the fl ue terminals of outdoor appliances 
according to AS5601-2004 (AGA gas installation code) or NZS 5261 (New Zealand)
 
                                                                                                                
Minimum 
 
   
 
Clearance 
(mm)
a  Below eaves, balconies or other projections:
 
- Appliances up to 50 MJ/h input 
300
 
- Appliances over 50 MJ/h input 
500
b  From the ground or above a balcony 
300
c  From a return wall or external corner 
500
d  From a gas meter (M) 
1000
e  From an electricity meter or fuse box (P) 
500
From a drain or soil pipe 
150
g  Horizontal from any building structure (unless appliance is approved 
 
for closer installation) or obstruction facing a terminal 
500
h  From any other fl ue terminal, cowl or combustion air intake 
500
Horizontally from an openable window, door, or non-mechanical air inlet, or 
 
any other opening into a building, with the exception of sub-fl oor ventilation 
 
(see also Note (I)):
 
- Appliances up to 150 MJ/h input 
500
 
- Appliances over 150 MJ/h input 
1500
k  Vertically below an openable window, door, or non-mechanical air inlet, 
 
or any other opening into a building, with the exception of sub-fl oor ventilation 
 
(see also Note (I)): see table below
NOTES: 
(I)  For mechanical air inlets, including spa blowers, the clearance 'j' and 'k' shall be 1500 mm in all cases.
(II)  All distances shall be measured vertically or horizontally along the wall to a point in line with the nearest par to of the terminal.
(III) Prohibited area below electricity meter or fuse box extends to ground level.
(IV) A fl ue terminal of this type shall not be located under a roofed area unless the roofed area is fully open on at least two sides and a free fl ow 
of air at the appliance is achieved.
Clearance 'k' in mm
Space Heaters  
                                      All Other Appliances
Up to 50 MJ/h 
Up to 50 MJ/h input  Over 50 MJ/h input 
Over 150 MJ/h input
      input 
 
  to 150 MJ/h input
      150 
500 
1000 
1500