Regency Bellavista™ B36X Gas Fireplace
INSTALLATION
Caution Requirements
The top, back and sides of the fi replace are defi ned by 
standoffs. The metal ends of the standoff may NOT be 
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk 
if these clearances (air space) to combustible materials are not 
adhered to. It is of greatest importance that this fi replace and vent 
system be installed only in accordance with these instructions.
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest 
importance that this fi replace and vent system be installed only in accordance with these instructions.
B36X Clearance Requirements
Minimum Vent Clearances
to Combustibles
Clearance:
Dimension
Measured From:
A: Mantel Height (min.)
6-1/2" (165mm)
Top of Fireplace Opening
B: Sidewall
12" (304mm) on one side
Side of Fireplace Opening
C: Ceiling
36-34" (933mm)
Top of Fireplace Opening
D: Mantel Depth
12" (304mm)
14-1/2 " (368mm)  from
Top of Fireplace Opening
E: Alcove Width
84" (2134mm)
Sidewall to Sidewall (Minimum)
 F: Alcove Depth
36" (914mm)
Front to Back Wall (Maximum)
Notes:
0"
No Hearth Required
Horizontal Top
2" (51mm)
Horizontal Side
1-1/2 " (38mm)
Horizontal Bottom
1-1/2" (38mm)
Vertical Vent
1-1/2" (38mm)