Initial Installation
Check draft
with a match
or smoke in
a 1⁄4" (6 mm)
tube located
here.
Warning:  Failure  to  position  the  parts  in  accordance  with  this  manual,  or  failure  to  use  only  parts 
specifically approved with this appliance may result in property damage or personal injury.
C
LEARANCES
 
TO
 C
OMBUSTIBLES
:
Mantle pillar to glass door 
 
 
 
9” (22.8 cm)
From floor to 8” wide mantle  
 
 
38” (96.5 cm)
Minimum non-combustible surface in front of unit  11” (27.9 cm)
Warning: Clearances must be sufficient to allow access for operation, maintenance and service. Stove 
must sit on a non-combustible surface.
Depth of unit into fireplace  16” (41 cm)
Depth of unit out of fireplace 3’’  (7.6 cm)
Minimum fireplace size: 
Width 34” (86.36 cm)
 
Height 21” (53.3 cm)
 
Depth 18” (45.7 cm)
B V
ENT
 M
ODEL
:
WARNING: This appliance has been designed to operate by drawing combustion air and dilution air 
from the room. It is also designed to draw room air for proper heat circulation from the sides of the 
unit. Blocking or modifying the louvers in any way can create hazardous situations, either through poor 
venting or by overheating. It is important that this unit has sufficient air circulation for proper venting 
and combustion. Provisions must be made for the supply of adequate combustion and ventilation air. 
These openings must not be blocked. The appliance must not be connected to a chimney flue servicing 
a separate solid fuel burning appliance.
A
UTOMATIC
 F
LUE
 G
AS
 S
PILL
 S
WITCH
:
NOTE: This heater must be properly connected to a venting system. This heater is equipped with a vent 
safety shutoff system designed to protect against improper venting of combustion products.  This safety 
switch is located on the rear of the appliance close to the draft hood relief opening. If the switch trips 
more than once, the venting should be inspected by a qualified service technician for possible blockage 
or severe down draft conditions.
BV Only: The draft hood must be in the same pressure zone as the air inlet.  To inspect draft from 
WARNING: Operation of this heater when not connected to a properly installed and maintained 
venting system can result in carbon monoxide (CO) poisoning and possible death.
the front of the unit, locate the 1⁄4” tube between 
the louvers (see Figure 13) and check for a draft 
using smoke. A vacuum or suction into the tube will 
indicate proper drafting. 
This  model  can  be  vented  with  4”  aluminum  or 
stainless steel flex vent and/or certified Type B Gas 
Vent. The flue collar of the appliance will fit inside 
of a standard 4” vent and may be fastened directly 
to  the  vent,  check  periodically  that  the  vent  is 
unrestricted and an adequate draft is present when 
the unit is in operation. 
Figure 13: Draft Check.