9-2. R.V. COIL CONTROL
Heating . . . . . . . . . . . . . . . . .  ON
 Cooling . . . . . . . . . . . . . . . . .  OFF
Dry . . . . . . . . . . . . . . . . . . . .  OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan
motor
Compressor
5 seconds
15 seconds
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
9-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor.
[ON]  The fan motor turns ON 5 seconds before the compressor starts up.
[OFF]  The fan motor turns OFF 15 seconds after the compressor has stopped running.
9-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor
Purpose
Actuator
Compressor
LEV
Outdoor fan 
motor
R.V.coil
Indoor fan 
motor
Discharge temperature 
thermistor
Protection
Indoor coil temperature 
thermistor
Cooling: Coil frost prevention
Heating: High pressure protec-
tion
Defrost thermistor
Heating: Defrosting
Fin temperature thermistor
Protection
Ambient temperature 
thermistor
Cooling: Low ambient tempera-
ture operation
Outdoor heat exchanger tem-
perature thermistor
Cooling: Low ambient tempera-
ture operation
Cooling: High pressure protec-
tion
ACTUATOR CONTROL
9
MUZ-GE25VA MUZ-GE25VAD MUZ-GE33VA MUZ-GE35VA MUZ-GE35VA2 MUZ-GE35VAD
MUZ-GE42VA MUZ-GE42VAD MUZ-GE50VA  MUZ-GE50VA2 MUZ-GE50VAD
MUZ-GE60VA MUZ-GE60VAD MUZ-GE71VA  MUZ-GE71VAD
MUZ-GE80VA MUZ-GE80VA2 MUZ-GE80VAD