Temperature and Humidity Ranges
The following table indicates the temperature and humidity ranges, within which the air conditioner can be used.
If the air conditioner is used at...
Then...
High temperature
The automatic protection feature may be triggered and
the air conditioner stopped.
the air conditioner stopped.
Low temperature
A water leakage or some other malfunction may happen if the heat
exchanger freezes.
exchanger freezes.
High humidity levels
Water may condense on and drip from the surface of the indoor unit if it is
used for a long period.
used for a long period.
1 Way cassette Slim 1 Way cassette
2 Way cassette
4 Way cassette
mini 4 Way cassette
DVM Model
AVMKH(C)
-
AVMGH(C)
AVMCH(C)
AVMC4
-
DVM PLUS II Model
AVXC1
AVXCS
AVXC2
AVXC4
AVXCM
BAC Model
KH(C)EAM
-
GH(C)EAM
CH(C)EAM
CH(C)EZM
CH(C)EZM
-
BAC Inverter Model
KHEAV
SHEAV
-
CHEAV
THEAV
Free Joint Multi Model
MHFK
-
-
-
MHFM
Mode
Outdoor
Temperature
Indoor
Temperature
Indoor
Humidity
Remark
Heating
-20°C/-4°F to 24°C/75°F
27°C/81°F or less
-
DVM PLUS II, BAC Inverter(UH052/060/070EAV1)
-5°C/23°F to 24°C/75°F
15°C/59°F to 27°C/81°F
BAC
-15°C/5°F to 24°C/75°F
27°C/81°F or less
Free Joint Multi, DVM, BAC Inverter(UH026/035EAV1)
-10°C/14°F to 24°C/75°F
27°C/81°F or less
BAC Inverter
Cooling
-5°C/23°F to 43°C/109°F
18°C/64 to 32°C/90°F
80% or less
DVM, DVM PLUS II, BAC Inverter
-5°C/23°F to 43°C/109°F 21°C/70°F to 32°C/90°F
BAC, Free Joint Multi
-10°C/14°F to 43°C/109°F 18°C/64 to 32°C/90°F
BAC Inverter(UH026/035EAV1)
-15°C/5°F to 43°C/109°F
18°C/64 to 32°C/90°F
BAC Inverter(UH052/060/070EAV1)
Drying
-5°C/23°F to 43°C/109°F
18°C/64 to 32°C/90°F
-
DVM, DVM PLUS
II, Free Joint Multi, BAC Inverter
-5°C/23°F to 43°C/109°F 21°C/70°F to 32°C/90°F
BAC
-10°C/14°F to 43°C/109°F 18°C/64 to 32°C/90°F
BAC Inverter(UH026/035EAV1)
-15°C/5°F to 43°C/109°F
18°C/64 to 32°C/90°F
BAC Inverter(UH052/060/070EAV1)
The standardized temperature for heating is 7°C/45°F. If the outdoor temperature drops to 0°C/32°F or below,
the heating capacity can be reduced depending on the temperature condition.
If the cooling operation is used at over 32°C/90°F(indoor temperature), it does not cool at its full capacity.
If the cooling operation is used at over 32°C/90°F(indoor temperature), it does not cool at its full capacity.
Cassette Type_E_26442.indd 11