Sanyo THX1252 用户手册

下载
页码 114
2-2
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Remote Control Functions
1. Main Operating Functions
1. Room Temperature Control
The thermostat is turned ON/OFF according to   as shown below.
 
 T = Room temperature - Set temperature
When remote controller sensor 
is used
Room temperature = Temperature detected by the remote controller sensor
When body sensor is used
Room temperature = Temperature detected by the body sensor - Intake shift temperature*
*  Intake shift temperature (enabled only during heating)
During heating, a difference in temperature occurs between the top and bottom of a room. This value is set in consideration for 
the difference between the temperature detected by the body sensor and the temperature at the bottom of the room.
<Value set for intake shift temperature at time of shipment>: 39°F (4°C)
Note:  The shift temperature can be selected in the range of 32 – 50°F (0 – 10°C), by using the remote controller simplifi ed set-
ting mode.
Cooling
Room temperature
Set temperature
–2
+2
+4
(deg)
T
Thermostat
ON
ON
OFF
Heating
Room temperature
Set temperature
–4
–2
+2
(deg)
T
Thermostat
ON
ON
OFF
(1)  After the thermostat turns ON, it will not turn OFF again as a result of   for 5 minutes.
(2)  After the thermostat turns OFF, it will not turn ON again for 3 minutes. (It also will not turn ON for 3 minutes after the power 
is switched ON.)
(3)  The compressor turns OFF if the mode is changed cooling 
 heating (or heating 
 cooling) while the compressor is ON.
(4)  If “test run” mode is selected, the thermostat will not turn OFF as a result of   for 60 minutes. (The thermostat is forced ON.)
SM830157_W-2WAY_ECO-i.indb   2
SM830157_W-2WAY_ECO-i.indb   2
2007/06/08   14:23:19
2007/06/08   14:23:19