Toshiba RAV-SM404SDT-E 用户手册

下载
页码 226
– 177 –
A
B
A
B
Terminal block for remote controller 
wiring of indoor unit
Terminal block
Remote controller 
unit
Remote controller wire 
(Procured locally)
A
B
1
1
L
N
2
2
3
3
220-2400V~
Remote controller
Remote controller 
wiring
Indoor side
Indoor/Outdoor 
connecting wires
Outdoor side
A
B
1
2
3
A
B
1
1
L
N
2
2
3
3
220-240V~
Remote controller
Remote controller 
wiring
Indoor side
Indoor/Outdoor 
connecting wires
Outdoor side
Remote controller 
inter-unit wiring
Indoor power 
inter-unit wiring
Indoor side
A
B
1
2
3
A
B
1
1
L
N
2
2
3
3
220-240V~
Remote controller
Remote controller 
wiring
Indoor side
Indoor/Outdoor 
connecting wires
Outdoor side
Remote controller 
inter-unit wiring
Indoor power 
inter-unit wiring
Indoor side
A B
1 2 3
A B
1
1
L N
2
2
3
3
A B
1 2 3
 
220-240V~
Remote controller
Remote controller 
wiring
Indoor side
Indoor/Outdoor 
connecting wires
Outdoor side
Indoor side
Indoor side
Remote controller 
inter-unit wiring
Remote controller 
inter-unit wiring
Indoor power 
inter-unit wiring
Indoor power 
inter-unit wiring
Revised 2: Jun., 2008
n
RAV-SP1104AT-E, RAV-SP1404AT-E
<Synchronous twin system>
13-3. Remote Controller Wiring
• Strip off approx. 9 mm the wire to be connected.
• For single system, use non polarity, 2 core wire is
used for wiring of the remote controller.
(0.5 mm² to 2.0 mm² wires)
• For the synchronous twin, triple system, use
2-conre shield wire (Vinyl cord for microphone 0.5
to 2.0 mm²) to conform to the EMC standard.
Wiring diagram
For details of wiring/installation of the remote
controller, refer to the Installation Manual enclosed
with the remote controller.
<Single system>
<Synchronous triple system>
Use 2-core shield wire (Vinyl cord for microphone
0.5 to 2.0 mm² or more) for the remote controller
wiring in the synchronous triple system to prevent
noise problems.  Be sure to connect both ends of
the shield wire to the earth.
Connect earth wire for each indoor unit in the
synchronous triple system.
n
RAV-SM1603AT-E
  WARNING
For  synchronous twin and synchronous triple systems, perform the following to confom to EMC standards.
<Synchronous twin system>