Unitary Products Group
FACTORY-INSTALLED OPTIONS
• SINGLE INPUT ELECTRONIC ENTHALPY 
ECONOMIZERS - Includes a slide-in / plug-in damper 
assembly with fully modulating spring-return motor 
actuator capable of introducing up to 100% outdoor air 
with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors 
the outdoor air and determines when the air is cool 
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must 
be field-assembled before installing.
• POWER EXHAUST - Our single economizer options are 
available with power exhaust. Whenever the outdoor air 
intake dampers are opened for free cooling, the exhaust 
fan will be energized to prevent the conditioned space 
from being over-pressurized during economizer operation.
The exhaust fan, motor and controls are installed and 
wired at the factory. The rain hood must be assembled 
and installed in the field.
• MOTORIZED OUTDOOR AIR INTAKE DAMPER - 
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a 
pre-set position whenever the supply air blower is 
operating and will drive fully closed when the blower unit 
shuts down.
The rain hood is painted to match the basic unit and must 
be field assembled before installing.
• PHENOLIC COATED EVAPORATOR, REHEAT, AND 
CONDENSER COILS - Special coating process that 
utilizes Technicoat 10-1" processes. Coating is applied by 
total immersion of the complete coil for maximum 
protection.
• ELECTRIC HEATERS wired for single point power 
supply. These nickel chromium heater elements are 
provided with limit and automatic reset capability to 
prevent operation at excessive temperatures.
• VARIABLE AIR VOLUME (VAV) - A factory-installed 
variable frequency drive (VFD), mounted in the Blower 
Access compartment, is used to control the speed of the 
indoor blower motor in order to maintain a constant static 
pressure in the supply duct. A pressure transducer and 
VAV control board are mounted inside the control box. 
The drive comes completely wired and pre-programmed 
from the factory.
An optional, factory-installed manual bypass switch avail-
able with factory-installed VFD can be found in the Blower 
Motor Access compartment. The switch can be used to 
either route power to the VFD for modulating control of the 
blower motor, to bypass the drive and operate the motor 
at full speed, or to power the drive (and not the motor) for 
diagnostic purposes.
Due to space limitations, VAV is not available with any of 
the factory-installed BAS options described below, but is 
available with ‘BAS-ready’ models. Terminal blocks are 
provided in the control box for field wiring of the customer-
installed BAS.
A ‘VFD-ready’ option provides the provisions for a cus-
tomer-installed drive. The unit comes with a mounting 
bracket installed in the Blower Access compartment which 
may accommodate other vendor’s drives depending on 
their size. In order to utilize the unit’s mounting bracket, 
the maximum recommended drive dimensions are as fol-
lows:
For 5-hp motor applications ........................13” H x 6” W x 7” D
For 7.5 thru 15-hp motor applications .........13” H x 8” W x 8” D
If the customer-installed drive will not fit in the allotted 
space, then it will have to be mounted within a NEMA-4 
enclosure for outside installation or inside the building on 
a perpendicular wall not subjected to excessive tempera-
ture, vibration, humidity, dust, corrosive gas, explosive 
gas, etc.
A terminal block located in the control box is provided for 
field connection of the VFD controls.
HOT GAS BYPASS - To allow for low cooling load opera-
tion, a direct-acting pressure-modulating bypass control 
valve installed on the system #1 discharge line is used to 
divert high temperature, high pressure refrigerant around 
the TXV in order to maintain a desired minimum evaporator 
pressure. HGBP is standard on all units with VAV and 
optional with CV units.
• FILTER OPTIONS - Standard units are shipped with 2” 
throw-away filters installed. 2” pleated and 4” pleated 
filters are offered as a factory installed option.
• CONVENIENCE OUTLET - This 110 volt outlet can be 
“powered” by the unit with a stepdown transformer or you 
may order the unit with a “non-powered” convenience 
outlet that can be wired in the field.
• DISCONNECT SWITCH - For gas heat units and cooling 
units with electric heat, a HACR breaker sized to the unit 
is provided. For cooling only units, a switch sized to the 
largest electric heat available for the particular unit is 
provided. Factory installed option only.
• DOUBLE WALL CONSTRUCTION - Optional double wall 
construction is available to provide smooth inner surfaces 
for easy and effective cleaning to reduce risk of dirt and 
bacterial accumulation. Fiberglass insulation is 
sandwiched between heavy gauge steel sheets to form a 
durable, rigid casing to withstand higher working 
pressures and impact forces. The heavy-duty construction 
provides excellent acoustic and thermal insulation and 
eliminates erosion of insulation material and 
contamination of the air stream.
• BAS - Building Automation System Controls 
(available on two-system cooling product only).
Simplicity® INTELLI-Comfort™ CONTROL - The York® 
Simplicity® INTELLI-Comfort™ control is factory installed. 
It includes a supply air sensor, a return air sensor, and an 
outside air sensor. There are provisions for a field installed 
dirty filter indicator switch, an air-proving switch, an Out-
side Air Humidity sensor, a Return Air Humidity sensor, an 
Inside IAQ sensor, and an Outside Air IAQ sensor. Con-