York D1EE036 用户手册

下载
页码 32
036-21411-002-A-0204
Unitary Products Group
21
TABLE 22: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ BELT DRIVE DEE060
MODEL
DEE
POWER
SUPPLY
HEATER
ACCESSORY
MODEL
NUMBER
SUPPLY
AIR
BLOWER
MOTOR
FLA
ELECTRIC HEATERS
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE
1
AMPS
MAX.
SIZE
HACR
2
BREAKER
AMPS
kW
STAGES
TOTAL
AMPS
060
208-1-60
2CE04500525
3
8.6
4.0
1
19.1
51.0
80
80
2CE04500725
3
5.6
1
27.1
51.0
80
80
2CE04501025
8.0
1
38.3
58.6
80
80
2CE04501525
11.9
2
57.4
82.5
90
90
2CE04502025
15.9
2
76.6
106.4
110
110
2CE04503025
22.2
2
106.9
144.4
150
150
230-1-60
2CE04500525
3
8.6
5.3
1
22.1
51.0
80
80
2CE04500725
3
7.5
1
31.3
51.0
80
80
2CE04501025
10.6
1
44.2
66.0
80
80
2CE04501525
15.9
2
66.3
93.6
100
100
2CE04502025
21.2
2
88.3
121.1
125
125
2CE04503025
29.6
2
123.3
164.9
175
175
208-3-60
2CE04500525
3
6.0
4.0
1
11.0
32.4
50
50
2CE04500725
3
5.6
1
15.6
32.4
50
50
2CE04501025
8.0
1
22.1
35.1
50
50
2CE04501525
11.9
2
33.1
48.9
50
50
2CE04502025
15.9
2
44.2
62.7
70
70
2CE04503025
22.2
2
61.7
84.6
90
90
230-3-60
2CE04500525
3
6.0
5.3
1
12.7
32.4
50
50
2CE04500725
3
7.5
1
18.0
32.4
50
50
2CE04501025
10.6
1
25.5
39.4
50
50
2CE04501525
15.9
2
38.2
55.3
60
60
2CE04502025
21.2
2
51.0
71.2
80
80
2CE04503025
29.6
2
71.2
96.5
100
100
460-3-60
2CE04500746
3
3.0
6.8
1
8.2
16.4
25
25
2CE04501046
3
10.1
1
12.1
18.9
25
25
2CE04501546
3
13.6
1
16.4
24.2
25
25
2CE04502046
3
19.5
2
23.5
33.1
35
35
2CE04503046
3
28.8
2
34.6
47.1
50
50
575-3-60
2CE04501058
2.4
10.6
1
10.2
15.7
20
20
2CE04501558
15.9
1
15.3
22.1
25
25
2CE04502058
21.2
2
20.4
28.5
30
30
2CE04503058
30.4
2
29.3
39.6
40
40
1.
Dual element, time delay type.
2.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
3.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago) see Table 19 for 
fuse block accessories available for field installation.