York 036-21103-003 用户手册

下载
页码 16
036-21103-003 Rev. A (0403)
Unitary Products Group
11
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the 
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
H1RA036S78A
INDOOR COIL MODEL NO.
G2FD036S17
CONDENSER
ENTERING AIR
TEMPERATURE
IDCFM
1050
1250
1450
ID DB (°F)
85
80
70
85
80
70
85
80
70
ID WB (°F)
72
67
57
72
67
57
72
67
57
75
T.C.
38.7
36.8
35.0
39.1
34.7
35.6
39.4
32.5
36.2
S.C.
23.4
23.5
23.4
24.4
24.8
24.8
25.4
26.1
26.2
K.W
3.30
3.25
3.21
3.59
3.54
3.50
3.48
3.43
3.39
85
T.C.
37.4
34.8
31.9
37.7
34.1
32.6
38.1
33.4
33.4
S.C.
23.5
24.0
22.2
24.7
25.2
23.9
25.9
26.4
25.5
K.W
3.74
3.65
1.95
4.06
4.00
3.90
4.00
3.94
3.84
95
T.C.
36.0
32.7
28.7
36.4
33.5
29.6
36.7
34.3
30.5
S.C.
23.6
24.5
21.0
25.0
25.6
22.9
26.4
26.7
24.8
K.W
3.80
3.67
3.51
4.09
3.99
3.83
3.99
3.92
3.76
105
T.C.
32.6
29.1
25.5
33.2
29.9
26.3
33.9
30.7
27.2
S.C.
22.6
22.1
19.6
24.3
23.6
21.5
26.1
25.2
23.3
K.W
4.17
4.00
3.85
4.53
4.36
4.21
4.49
4.32
4.17
115
T.C.
29.2
25.5
22.3
30.1
26.3
23.1
31.0
27.0
23.8
S.C.
21.5
19.6
18.2
23.6
21.6
20.0
25.7
23.6
21.8
K.W
4.16
3.95
3.81
4.50
4.27
4.12
4.45
4.19
4.04
125
T.C.
25.5
22.4
19.6
26.2
22.8
20.0
26.9
23.1
20.4
S.C.
20.3
18.8
17.4
22.3
20.5
18.9
24.3
22.2
20.3
K.W
4.29
4.12
3.99
4.65
4.43
4.29
4.61
4.35
4.20
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
N1AHB1293
G2FD036S17
1.00
1.00
1.00 
F2RP036N93
1.02
1.02
1.01