DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets  
555-230-112  
Issue 5
May 1998
Install and Connect Cabinets 
Page 1-6
Connect AC Power and Ground 
1
Connect AC Power and Ground
Power Requirements
Table 1-2
 shows the power requirements. 
J58890CE-1, J58890CE-2, and J58890CH-1
The following procedures apply to the AC-powered PPN and EPN cabinets. 
Either of the following power sources can supply 60 Hz power to the AC load in 
Release 5 and later systems: 
Single-phase, 4-wire, 120/240 VAC supplying 240 VAC. This source has 2 
hot wires, 1 ground wire, and 1 neutral wire (J58890CE).
3-phase, 4-wire, 120/208 VAC supplying 208 VAC. This source has 2 hot 
wires, 1 ground wire, and 1 neutral wire (J58890CE).
Single-phase, 3-wire, 208 or 240 VAC. This source has 2 hot wires and 1 
ground wire (J58890CH).
Either of the following power sources can supply 50 Hz power to the AC load in 
Release 5 and later systems:
Non-United States 4-wire, Y, 220/380 VAC. This source has 3 hot wires, 1 
neutral wire, and 1 ground wire.
Non-United States Delta, 3-wire, 220 or 240 VAC. This source has 3 wires.
Table 1-2.
DEFINITY System Power Requirements
Maximum DEFINITY UL Rating Label Power Capacity
Vac 
I
n
Iac 
I
n
Max  W 
I
n
BTU/Hr
208
24
3245
11071.26
240
21
3276
11177.71
120
40
3120
10645.44