Install Telecommunications Cabling 
Page 2-5
Installation Requirements 
2
Installation Requirements
Sneak Fuse Panels and Emergency Transfer Units
Approximately 8 inches (20 cm) of horizontal wall space is required for each 
column of sneak fuse panels. Up to 25 connector pairs can be protected by each 
panel. Horizontal wall space must also be provided for emergency transfer units.
110-Type Hardware
The trunk/auxiliary field and the distribution field are mounted on the same wall. 
Each 110P-type terminal block is 8.5 inches (21.6 cm) wide. Vertical patch cord 
troughs are 5.31 inches (13.4 cm) wide and horizontal patch cord troughs are 23 
inches (58.4 cm) wide.
Each 110A-type terminal block is 10.81 inches (27.4 cm) wide; however, no 
horizontal patch cord troughs are used and the blocks are shorter than 
110P-type terminal blocks. This allows the 110A-type terminal blocks to be 
stacked. Therefore, the 110A-type hardware requires less space than the 
110P-type hardware on a per-station basis.
Cable Slack Manager 
A Cable Slack Manager is 32 inches (81.3 cm) wide. The quantity of which is 
determined by dividing the total length of the MDF in inches (cm) by 32 (81.3). A 
partial number of 0.4 or less should be rounded down, and a partial number of 
0.5 or more should be rounded up (for example: 2.4 =  2 cable slack managers 
and 2.5 = 3 cable slack managers).
NOTE:
Cable clamps are required in installations with cable slack managers. At 
the rear of the cabinets, on each rear ground plate, install 2 cable clamps 
using the screws provided. These clamps hold the 25-pair input/output or 
MDF cables in place.