Install Telecommunications Cabling 
Page 2-25
Cable Installation 
2
Install Connector Cables Between Auxiliary 
Cabinet and MDF
Auxiliary equipment that connects to the MDF can be mounted inside the 
Auxiliary cabinet. The equipment connects to an ED-1E1443-10 (Group 1) 
intraconnection panel mounted in the cabinet. This intraconnection panel 
consists of a 110-type 100-pair wiring block. Auxiliary equipment is connected to 
the 110-type wiring block. The wiring block is pre-wired to four 25-pair female 
connectors mounted on the outside rear of the cabinet.
1. Install “D” rings on the wall between the cable slack manager and the 
terminal/connecting blocks mounted on the MDF.
2. Install a self-sticking port label on the rear of each connector on the B25A 
connector cable. See 
Figure 2-9 on page 2-17
.
NOTE:
Labels should be positioned so they will not be obscured by the 
cabinet connector retainers.
3. At the rear of the Auxiliary cabinet, connect 1 end of the connector cable 
to the assigned connector.
4. Route the cable down the rear of the cabinet and through the cable slack 
manager to the MDF.
5. At the MDF, connect the other end of the cable to the assigned 
terminal/connecting block connector.
6. Store the excess cable in the cable slack manager.
7. Repeat Steps 2 through 6 until all cables are installed.