Heatcraft Refrigeration Products 25000102 用户手册

下载
页码 36
Parallel Compressor Systems Installation & Operations Manual, October 2004  
25
Parallel Compressor Systems
Series P100 Pressure Control
The P100 series, manufactured by Johnson Control, Inc., are 
encapsulated, non adjustable, single-pole single throw, direct 
mount pressure controls typically used for low or high pressure 
cutouts. On the Heatcraft manufactured parallel systems, the 
control is used for High Pressure cutout. 
There are two types available. Auto Reset Models and Manual 
Reset Models.
Auto Reset Models
When pressurized to the selected actuation pressure setting, 
the internal snap-acting disc reverses its shape and drives 
a set of electrical contacts either open or closed. When the 
pressure drops below the de-actuation pressure setting, the 
disc snaps back to its preset position thus resetting the electrical 
contacts. 
Manual Reset Models
The snap-acting disc in the manual reset model opens the 
electrical contacts when actuated by the pressure sensor. Once 
the disc snaps, the contacts are held open until an external 
force on the push button closes them. Because of the disc’s link 
with the pressure sensor, the contacts cannot be reset until the 
pressure drops to a predetermined level. 
The latching mechanism inside the manual reset model is trip 
free. The electrical contacts will cutout even if the reset button 
is held fully depressed. The control can only be reset when the 
pressure returns to a predetermined level.
Liquid Level Switch
S-9400 Level Switch Series
OPTION – Not available on all systems or receivers.
Operation
The  S-9400  Series  Level  Switches  manufactured  by AC&R 
C
omponents
 uses light reflecting from a conical glass prism as 
a means of detecting the absence of a fluid at the level of the 
glass cone. When no fluid covers the lower half of the cone, 
infra-red light from the module reflects from the mirror-like 
inner surface of the cone back to a light detector signaling the 
electronic module to switch. When fluid covers the lower half  
of the glass cone, the light from the module passes into the 
fluid. This absence of light is detected by the module which 
switches into the opposite direction. The module provides a 
.06/.10 differential distance from the cone point down.
Figure 13.
Figure 14.
Table 19. Level Switch Table
Cat.
No.
Voltage
Resistive
Rating
Contacts
Liq. Present
S-9420
208/240
50/60 Hz
.5 Amp
N.C.
Cat.
No.
Wire Color
Code
Replacement
Module No.
Replacement
Sight Glass
No.
S-9420
Red & White
2-044-015
3-020-063