Observe the compressor 
suction & discharge 
pressures
Are pressures 
changing with the 
modulation 
cycle?
Operation 
is normal
Yes
No
Yes
Yes
Measure the resistance 
of the coil
Is the compressor 
running?
Is the compressor 
overheated?
Perform troubleshooting 
to determine why the 
compressor isn’t 
running
Allow time to cool
Put the system back into 
operation and retest
Start
Measure the voltage at 
the modulation coil 
terminals
Is voltage present,
coinciding with the 
modulation cycle?
Troubleshoot the 
modulation control
WARNING!
Disconnect and lockout 
the power before 
proceeding
Remove one wire from 
the modulation coil
Coil has continuity 
and isn’t grounded?
Replace modulation 
coil
Replace modulation 
valve, follow valve 
replacement 
instructions
Put the system back into 
operation and retest
No
No
No
Yes
No
Yes
Figure 10 
Modulation Troubleshooting