MGE UPS SYSTEMS -  5102933200/AA
Troubleshooting
Operating anomalies
If the green light on the communication card
remains off :
  check that the card is correctly inserted in
the slot and that its cover is well screwed on,
  check the power supply of the UPS or
MultiSlot,
  remove and re-seat the card.
If the green light on the communication card
remains on more than 3 minutes :
  check that the card is correctly inserted in
the slot and that its cover is well screwed on,
  remove and re-seat the card.
If a communication fault is detected by
Solution-Pac software or by UPS
control:
  check that the communication cable is
correctly connected on both sides,
  remove and re-seat the card.
If the problem continues, contact our
after-sales support department.
Fig. 7
Cable replacement
If the communication cable is lost or
damaged, a cable wired as indicated in
Fig. 7 for the connection to a UPS,
or in Fig. 8 for the connection to UPS
control,
may be used.
male DB9
connector
DB9/DB9cable
female DB9
connector
DB9/DB9 cable wiring diagram
male DB9
connector
female DB9
connector
2
3
5
6
2
3
4
5
6
7
8
shielded
cable
frame
frame
male DB9
connector
DB9/RJ45 cable
male RJ45
connector
DB9/RJ45 cable wiring diagram
male DB9
connector
male RJ45
connector
2
3
5
6
5
8
4
7
Fig. 8