GE GFK-1918D 用户手册
G E F a n u c P L C Ta r g e t s
Configuring Communication
GFK-1918D
CIMPLICITY Logic Developer - PLC Version 4.00
29
Set up a permanent IP address. For more information, see “To set a permanent IP
address for a PACSystems™ RX7i”.
address for a PACSystems™ RX7i”.
To set a tem po ra r y I P ad dr ess f or a PA CS ys tem s™ RX 7i
1.
In the
Utilities tab of the
Navigator, double-click
Set Temporary IP Address.
The Set Temporary IP Address dialog box appears.
2.
In the MAC Address field, specify the MAC address for the PACSystems™ RX7i.
3.
In the IP Address to Set field, specify the temporary IP address you want to set on the PACSystems™ RX7i.
4.
If required, select the Network Interface Selection check box and specify the network interface the PACSystems™
RX7i is located on.
RX7i is located on.
5.
Click the Set IP button.
The IP address of the specified PLC or device is temporarily set to the indicated
address.
address.
Warning: The IP address set by the Set Temporary IP Address utility will not be
retained through a power cycle. If you want to set a permanent IP address, you
must do so by other methods.
retained through a power cycle. If you want to set a permanent IP address, you
must do so by other methods.