Select Add GBCs for Genius Redundancy.
4.
Click Next and follow the wizard to the end. The wizard allows you to select a Genius redundancy scheme and the
location of the GBC modules. You can run this wizard multiple times to configure additional pairs of redundant
busses in the same system.
location of the GBC modules. You can run this wizard multiple times to configure additional pairs of redundant
busses in the same system.
Note: When you add a Genius Bus Controller (GBC) to a Series 90™-70 rack, a
new Genius bus network is automatically created and associated with that slot and
GBC module. Up to 31 Genius I/O devices (blocks) can be connected to a GBC
through its Genius bus.
new Genius bus network is automatically created and associated with that slot and
GBC module. Up to 31 Genius I/O devices (blocks) can be connected to a GBC
through its Genius bus.
Co nfig ur ing th e s eco nd ar y h ar dw ar e c on fig ur at ion (S eri es 9 0™ - 70 o nly)
1.
In the
Project tab of the
Navigator, select the
Hardware Configuration folder.
2.
Right-click Hardware Configuration, point to Redundancy, and choose Mirror to Secondary Hardware
Configuration.
Configuration.
A secondary rack system that is a copy of the primary rack system is generated.
The target now displays two Hardware Configurations (HWCs), one labeled
[Primary] and the other, [Secondary]. The Primary HWC is bolded because it is
currently selected. The target property, Dual HWC, is now set to True.
The target now displays two Hardware Configurations (HWCs), one labeled
[Primary] and the other, [Secondary]. The Primary HWC is bolded because it is
currently selected. The target property, Dual HWC, is now set to True.