System Sensor M500S 用户手册

下载
页码 4
SS-460-001 
I56-3850-002
figUre 3. TYpiCaL nOTifiCaTiOn appLianCe CirCUiT COnfigUraTiOn, nfpa STYLe Y:
(+)
(+)
(+)
(+)
(+)
(+)
47K EOL
RESISTOR
ELR-47K
UL LISTED EOL RELAY 
SHOWN ENERGIZED
24 VDC COIL EOLR-1
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE 
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
TO NEXT CONTROL MODULE OR END-OF-LINE 
RELAY. ONE RELAY REQUIRED FOR EACH 
CIRCUIT. SOME CONTROL PANELS HAVE RELAY 
BUILT IN AND DO NOT REQUIRE EXTERNAL 
WIRING. REFER TO PANEL MANUAL.
24 VDC POWER SUPPLY
ISOLATED, REGULATED, 
POWER LIMITED PER NFPA 70. 
LISTED FOR FIRE PROTECTION 
WITH BATTERY BACKUP.
MODULE POLARITIES ARE 
SHOWN IN ALARM
CONNECT MODULES TO 
LISTED COMPATIBLE 
CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED 
AND POWER LIMITED
CONTROL 
MODULE
FROM 
PANEL OR 
PREVIOUS 
DEVICE
TO NEXT 
DEVICE
*NOTE: ANY FAULT IN THE POWER SUPPLY IS 
LIMITED TO THAT ZONE AND DOES NOT 
RESULT IN A FAULT IN A SEPARATE ZONE.
(−)
(−)
(−)
(−)
(−)
(−)
C0913-05
figUre 4. TYpiCaL faULT TOLeranT nOTifiCaTiOn appLianCe CirCUiT COnfigUraTiOn, nfpa STYLe Z:
(+)
(–)
(+)
(–)
(+)
(–)
(–)
(+)
(–)
(+)
(+)
(–)
ALL WIRING SHOWN IS SUPERVISED 
AND POWER LIMITED
MODULE POLARITIES ARE 
SHOWN IN ALARM
EOL RESISTOR 
IS INTERNAL AT 
TERMINALS
8 & 9 
UL LISTED EOL 
RELAY SHOWN 
ENERGIZED
24 VDC COIL 
EOLR-1
TO NEXT CONTROL MODULE OR 
END-OF-LINE RELAY. ONE RELAY 
REQUIRED FOR EACH CIRCUIT. 
SOME CONTROL PANELS HAVE 
RELAY BUILT IN AND DO NOT 
REQUIRE EXTERNAL WIRING. 
REFER TO PANEL MANUAL.
CONTROL 
MODULE
TO 
NEXT 
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX. TWISTED PAIR
IS RECOMMENDED
CONNECT MODULES TO LISTED 
COMPATIBLE CONTROL PANELS ONLY
FROM 
PANEL OR 
PREVIOUS 
DEVICE
24 VDC CIRCUIT
DO NOT LOOP WIRE ON TERMINALS 10 & 11. 
BREAK WIRE RUN TO PROVIDE SUPERVISION 
OF CONNECTIONS.
24 VDC POWER SUPPLY
ISOLATED, REGULATED, POWER 
LIMITED PER NFPA 70. LISTED 
FOR FIRE PROTECTION WITH 
BATTERY BACKUP.
*NOTE: ANY FAULT IN THE POWER SUPPLY 
IS LIMITED TO THAT ZONE AND DOES NOT 
RESULT IN A FAULT IN A SEPARATE ZONE.
C0914-05