APC 6000 用户手册

下载
页码 38
Page 22 - 
6739389EN/FB
Unitary UPS
 (continued)
Main status bits (UPS operating information)
Normal
:
inverter powers load and full backup
bit 4C4 = 1
time available
Danger
:
inverter does not power load
bit 4C6 = 1
Downgraded
:
malfunction or environment fault
bit 4C5 = 1
Load on battery
:
fonctionnement en autonomie
bit 4C7 = 1
Normal operation
Operating modes
The following section describes the
different states of a
MGE
TM 
Galaxy
TM
 6000 UPS and
the addresses of the bits in the
system data array.
Normal:
bit 4C4 = 1
Danger:
bit 4C6 = 0
Downgraded:
bit 4C5 = malfunction dependent
Load on battery:
bit 4C7 = 0
Q1 closed:
bit 40E = 1
Rectifier/charger on:
bit 408 = 1
QF1 closed:
bit 400 = 1
Inverter connected:
bit 484 = 1
Q5N closed:
bit 498 = 1
Q3BP open:
bit 497 = 0
Q4S closed:
bit 496 = 1
SS open:
bit 499 = 0
K2S open (if available):
bit 494 = 0
Normal:
bit 4C4 = 1
Danger:
bit 4C6 = 0
Downgraded:
bit 4C5 = malfunction dependent
Load on battery:
bit 4C7 = 1
Q1 indifferent:
bit 40E = X (N/A)
Rectifier/charger off:
bit 408 = 0
QF1 closed:
bit 400 = 1
Inverter connected:
bit 484 = 1
Q5N closed:
bit 498 = 1
Q3BP open:
bit 497 = 0
Q4S closed:
bit 496 = 1
SS open:
bit 499 = 0
K2S open (if available):
bit 494 = 0
Load on battery