MGE UPS Systems EB 22XLA 用户手册
MGE UPS SYSTEMS
Pulsar ESV 8+/11+/14+/22+ EB 22/EB 22XLA : 86-153277-00
13
option 1
■
status information card: after the card is
installed in the rear of the Pulsar, communi-
cation port
cation port
15
transmits status information
on a SUB-D 9-pin female connector using
the following pinouts:
1 - ground,
4 - normal operation,
5 - common,
7 - low battery warning,
9 - operation on battery.
the following pinouts:
1 - ground,
4 - normal operation,
5 - common,
7 - low battery warning,
9 - operation on battery.
communication
The communication port 9 , at the rear of
Pulsar, delivers information in the form of
an RS232 serial link supported by the com-
munication protocol exclusive to
MGE UPS SYSTEMS. The Solution-Pac
programs use the data made available by
this protocol.
Pulsar, delivers information in the form of
an RS232 serial link supported by the com-
munication protocol exclusive to
MGE UPS SYSTEMS. The Solution-Pac
programs use the data made available by
this protocol.
9
V
I
5
4
3
2
1
9
8
7
6
0V
RD TD
1 - ground
2 - TD
3 - RD
5 - common
2 - TD
3 - RD
5 - common
ESV Driver software (included in the
CD-ROM: EMB/ESVPLUS/CONFIG) lets
you edit the default parameter of Pulsar:
CD-ROM: EMB/ESVPLUS/CONFIG) lets
you edit the default parameter of Pulsar:
■
battery test frequency
(default: every week);
■
nominal output voltage
(default: 120 Volts);
■
high/low voltage thresholds
(defaut: 138/92 Volts);
■
Fader/Booster activation thresholds
(defaut : 102/128 Volts);
■
on/off conditions:
■
■
automatic restart,
■
■
forced reboot,
■
■
energy saving,
■
■
cold start.
15
n.o.
n.c.
n.o.
5
4
3
2
1
9
8
7
6
0V
0V
0V
Relay breaking capacity:
Vmax = 25V DC, Imax = 10mA
n.o. : normally open,
n.c. : normally closed.
Vmax = 25V DC, Imax = 10mA
n.o. : normally open,
n.c. : normally closed.
option 2
■
SNMP card: after the card is installed in
the rear of the Pulsar, communication port
15 transmits information supported by the
SNMP protocol on an RJ45 or BNC
connector.
15 transmits information supported by the
SNMP protocol on an RJ45 or BNC
connector.
option 3
■
battery extension module Pulsar EB
22XLA (for Pulsar ESV 22+):
Switch off Pulsar ESV 22+ (push
button 3 ), disconnect the input
connection cord 5 .
Connect battery connection cord
Switch off Pulsar ESV 22+ (push
button 3 ), disconnect the input
connection cord 5 .
Connect battery connection cord
19
(included with Pulsar EB 22XLA) to Pulsar
EB 22 and connect to Pulsar EB 22XLA.
You can connect 7 Pulsar EB 22XLA in
parallel.
EB 22 and connect to Pulsar EB 22XLA.
You can connect 7 Pulsar EB 22XLA in
parallel.