4. Advanced Operations 
Configuring Traps 
SNMP Trap Command Summary  
Command Description 
Set Trap EM Status 
Enables or disables the Environmental Monitor Status trap 
Set Trap THS Status 
Enables or disables a temperature/humidity sensor Status trap 
Set Trap THS Temp 
Enables or disables a temperature/humidity sensor Temp trap 
Set Trap THS Temphigh 
Sets a temperature/humidity sensor Temp trap high limit 
Set Trap THS Templow 
Sets a temperature/humidity sensor Temp trap low limit 
Set Trap THS Humid 
Enables or disables a temperature/humidity sensor Humid trap 
Set Trap THS Humidhigh 
Sets a temperature/humidity sensor Humid trap high limit 
Set Trap Tower Status 
Enables or disables the Tower Status trap 
Set Trap Infeed Status 
Enables or disables the Infeed Status trap off 
Set Trap Infeed Load 
Enables or disables the Infeed Load trap 
Set Trap Infeed HighThresh 
Sets the Infeed Load trap high limit 
Set Trap Outlet Change 
Enables or disables the Outlet Change trap 
Set Trap Outlet Status 
Enables or disables the Outlet Status trap 
Show Traps 
Displays trap configurations 
Enabling or Disabling a Status trap 
The Set Trap … Status command is used to enable or disable Status traps for a Tower, Infeed, Outlet, 
Environmental Monitor or Sensor. 
To Enable or Disable a Status trap: 
At the Switched PDU: prompt, type 
set trap
 (
tower
,
 infeed,
 
outlet, em 
or 
ths
status
, followed by the 
tower, infeed, outlet, Environmental Monitor or sensor name, and 
on
 or 
off
.
  
Press 
Enter
, or 
Type 
set trap 
(
tower
,
 infeed,
 
outlet, em 
or 
ths
status all
, followed by 
on 
or 
off 
and press 
Enter
Examples 
The following command enables the Status trap for the first tower, using the tower’s absolute name: 
Switched PDU: set trap tower status .a on<Enter> 
The following command enables the Status trap for the tower named Florida_HQ_1: 
Switched PDU: set trap tower status Florida_HQ_1 on<Enter> 
NOTE:  Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling 
an Outlet Status trap automatically enables the Infeed and Tower Status traps for that outlet.  Conversely, if a 
Tower Status trap is disabled, all associated Infeed Status & Load and Outlet Status traps will be disabled. 
Page 52 - 301-0399-4 Rev A.