3.7.  Reference parameter of the inverter
Reference parameter of the inverter is listed below.
Title
Name
Description
acc
Acceleration time
dec
Deceleration time
fh
Maximum frequency
ul
Upper limit frequency
ll
Lower limit frequency
vl
Base frequency 1
Do not change these parameters, because
the L
ON
W
ORKS
 option unit using them.
cmod
Command mode selection
Network command has priority when the
inverter is Remote mode. (See previous
section)
fmod
Setpoint mode selection
Network setpoint has priority when the
inverter is Remote mode. (See previous
section)
f111 
...
Logic input terminal function
Set proper value if use (See the inverter
instruction manual).
f603
Emergency stop selection
For “nviEmergOverride”
f800
Communication baud rate
Set “1” (default)
f801
Communication parity
Set “1” (default)
f803
Communication error trip time
Set properly value
f829
Communication protocol
Set “1” (MODBUS)
f851
Operation at network disconnection
See “section 7.4 Communication health
management”.
 Warning
Mandatory
For LIU007Z, set up “Communication error trip function (f803, see the inverter
instruction manual for details)” to stop the inverter when this option unit is deactivated
by an unusual event such as tripping, an operating error, power outage, failure, etc.
Deactivated option unit may cause an accident, if the “Communication error trip
function” is not properly set up.