Toshiba TOSVERT VF-FS1 Series 用户手册

下载
页码 38
E6581373
- 26 -
6.5.9.  nviParamCmd (Parameter access)
Input network variable
SNVT type: SNVT_preset (94)
It is used to access the inverter parameters. Refer to section 7.5 “Parameter access method” for the
example usage.
- Valid range: All accessible parameters in the inverter
- Format:
field
Length
Description
learn
1 byte
Command
0 (LN_RECALL)
: Not support
1 (LN_LEARN_CURRENT) : Not support
2 (LN_LEARN_VALUE)
: Write
3 (LN_REPORT_VALUE)
: Read
selector
2 bytes
Parameter address (unsigned value) 
*1
value[0]
1 byte
0
value[1]
1 byte
0
value[2]
1 byte
The most significant 2 hex bytes of data
value[3]
1 byte
The least significant 2 hex bytes of data
day
2 bytes
Invalid 
*2
hour
1 byte
Invalid 
*2
minute
1 byte
Invalid 
*2
second
1 byte
Invalid 
*2
millisecond
2 bytes
Invalid 
*2
*1: This value is Hexadecimal value, but it may be displayed with decimal value on network tool.
*2: The time fields (day, hour, minute, second and millisecond) are not supported by this option
unit. Any values in the time fields of the Parameter access command will be ignored.