Table 6.1   Control Functions
 
  No. 
Device 
Name / Function 
Normal Status 
During Operation 
Remarks 
 
c
 
 
52R 
Main circuit AC input circuit breaker 
When the AC input is normal, power is 
supplied to the UPS through this circuit 
breaker.
 
 
ON 
 
d
 
 
72B 
Main circuit DC input circuit breaker 
When AC input has been cut off, power is 
supplied from the battery to the UPS 
through this circuit breaker.
 
 
ON 
When the circuit breaker
is tripped in manual 
mode, reset it by grasping
the handle and pulling it 
down or to the right.
 
 
 
52C 
Bypass AC circuit breaker 
When bypass power is supplied, power is 
supplied to the load through this circuit 
breaker.
 
 
ON 
 
 
f
 
 
52M 
Maintenance bypass AC circuit breaker 
When bypass power is supplied for UPS 
maintenance, power is supplied to the 
load through this circuit breaker.
 
 
OFF 
 
 
g
 
 
52L 
AC output circuit breaker 
While UPS power or bypass power is 
supplied, power is supplied to the load 
through this circuit breaker.
 
 
ON 
 
 
h
 
 
8A 
Control power source switch 
When AC input is normal, pressing this 
switch supplies power to the control power
source.
 
 
ON 
Certain systems are 
also provided with the 
switch 8D.
 
 
i
 
 
6CH 
Precharge circuit button 
Pressing this button supplies power to the
circuit that precharges the DC electrolytic 
capacitor before power is supplied to   
circuit breaker 52R. 
 
ON 
 
 
6.2 Circuit 
Configuration 
 
 
 
 
 
Figure 6.2   Standard Circuit Configuration 
~ 
72B
52R 
UPS  
AC INPUT
 
BATTERY
 
BYPASS 
AC INPUT
 
52C
 
AC OUTPUT 
52L
52M