8.3.6  Changing to Floating Charge etc. (for MSE individual battery) 
Table 8.7 shows the procedure used to change manually from protective charge to floating 
charge. 
This operation does not apply to shared battery systems. 
(1)  An MSE battery normally operate in floating charge mode. 
(2) To prevent the battery temperature from rising, the mode changes automatically to 
protective charge mode when a "BATT FAULT1" (BATTERY OVER TEMP.) warning 
occurs. 
(3)  In protective charge mode, the battery is automatically charged at a voltage about 5% 
lower than normal (floating) charge when the battery temperature has risen above the 
rated value, in order to prevent deterioration caused by excessive charging at high 
temperatures. 
(4) After a set amount of time has elapsed (about 6 hours), if the "BATT FAULT1" 
(BATTERY OVER TEMP.) warning message has disappeared, the mode will 
automatically change back to floating charge. As a result, it will not normally be 
necessary to change the mode manually as described below. 
Table 8.7   Changing from Protective Charge to Floating Charge 
Step Procedure 
LCD/LED 
Status (After Execution) 
Check to make sure 
that the 
"PROTECTION" LED 
is lit.. 
Check to make sure 
that the 
"BATT FAULT1" 
warning message has 
disappeared. 
 
3 Hold 
down 
the 
"FLOAT" key (
h in 
Figure 6.3.1 on page 
14) for at least 0.5 
second. 
→ Change  to  floating 
charge is complete. 
The "FLOAT CHARGE" LED lit. 
The "PROTECTION" LED unlit. 
UPS SUPPLY
 
UPS SUPPLY
 
            AC-VO      200[V] 
            AC-
 
I
 
O        50[
%
           
            AC-VO      200[V] 
            AC-
 
I
 
O        50[
%
           
BATTERIES 
AC
 
SWITCH
 
UPS
 
BYPASS 
DISCHARGE
 
FLOAT CHARGE
 
PROTECTION
 
AC INPUT
CONVERTER
 
INVERTER
AC OUTPUT
BYPASS INPUT
BATTERIES 
AC
 
SWITCH
 
UPS
 
BYPASS 
DISCHARGE
 
FLOAT CHARGE
 
PROTECTION
 
AC INPUT
CONVERTER
 
INVERTER
AC OUTPUT
BYPASS INPUT