- 47 -
 
 
6 F 3 H 1 0 0 1
Table 9.7   Warning-3 (Operation control) 
# Item 
LCD 
Message 
Indication 
Description 
59C 
BYPASS OV 
Bypass input voltage is high. 
27C 
BYPASS UV 
Bypass input voltage is low. 
95C 
BYPASS ASY 
Bypass input frequency error. 
 
Table 9.8   Warning - 4 and 5 (Guidance) 
# Item 
LCD 
Message 
Indication 
Description 
49H 
LOAD LIMIT 
Load has exceeded prescribed level. 
51LI 
O/P OC (PEAK) 
Load current peak value is high. 
72BO 
72B MIS OPE. 
72B has gone off during operation.       
(Including operation error) 
26B 
BATT FAULT1 
Battery temperature has risen. 
33B 
BATT FAULT2 * 
Battery fluid level has gone below prescribed level. 
80B2 
BATT UV (ALM) 
Battery voltage is near discharged voltage. 
76CH 
BATT OC 
Charging current is high. 
47R 
AC PHASE ERR 
Phase ration of AC input is reserved.   
47C 
BYPASS ERR 
Phase ration of bypass input is reserved.   
10 
48S 
STARTUP ERR 
Startup was not completed. 
11 
52CO 
52C MIS OPE. 
52C has gone off during opearion. 
(Including operation error) 
12 
83F 
SWITCH ERR 
Changeover switch error. 
 
 
This message is deleted in case of a sealed type NS and HHS or MSE battery.