Toshiba VF-PS1 用户手册

下载
页码 10
 
E 6 5 8 1 3 6 4  
2.1.1. Switching circuit connection diagram, Time chart, 
Parameter settings 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Title 
Function 
Adjustment range 
Setting value 

Output signal selection of commercial 
power/inverter switching 
0 to 3 
2 or 3 

Commercial power/inverter switching 
frequency 
0 to  
Power supply frequency 

*3
Inverter side switching waiting time 
0.1 to 10.0 seconds 
Different for each model 

*3
Commercial power side switching waiting 
time 
0.37 to 10.0 seconds 
0.62 

Commercial power switching frequency 
holding time 
0.1 to 10.0 seconds 
2.0 

*1
Input terminal selection #6 (S2) 
0 to 135 
20 
(Emergency stop) 

Input terminal selection #7 (S3) 
0 to 135 
102 
(Commercial power run 
switching) 

Output terminal selection #1 (OUT1) 
0 to 119 
46 
(Commercial power/inverter 
switching output 1) 

Output terminal selection #2 (OUT2) 
0 to 119 
48 
(Commercial power/inverter 
switching output 2) 
*1:Be careful about Items 5 and 7 in 2.2, “Precautions.”
 
*2:Due to internal processing timing, inverter-side wait time become 0.5 second longer than the setting value of 
*3: and  are included the operation time of the relay and the magnet contactor.     
In almost all cases, it is not necessary to change these parameter settings.
 
Commercial power 
switching frequency 

Commercial power switching 
frequency hold time 
            
Commercial power 
run switching signal
          S3-CC
ON 
ON
ON
ON 
ON
ON
0Hz
ON
Inverter-side switching 
wait time 
*2
 
Frequency after speed is 
detected  
Commercial power   
switching wait time 

Speed detection time
Inverter run
Commercial power run 
Inverter run
Setting frequency
P24-OUT1(RY1) 
for inverter
 
run  
output 
P24-OUT2(RY2)
for commercial 
power run
 
output
      Run signal
           F-CC
Stand-by signal 
          ST-CC
F L 
FLA 
FLC 
FLX 
S3 
MC3 
MC1 
(Inverter) 
(Commercial 
power) 
S3 
RY1(Inverter) 
RY2(Commercial 
power) 
MC3 
Inverter protective 
action signal 
MC2 
MC2