Toshiba VF-FS1 用户手册

下载
页码 252
E6581381
L-1
12
12. Specifications
12.1 Models and their standard specifications
Standard specifications
Item
Specification
Input voltage
3-phase 200V
Applicable motor (kW)
0.4
0.75
1.5
2.2
4.0
5.5
7.5
11
15
18.5
22
30
Type
VFFS1
Form
2004PM 2007PM 2015PM 2022PM 2037PM 2055PM 2075PM 2110PM 2150PM 2185PM 2220PM 2300PM
Capacity (kVA) Note 1)
1.1
1.8
2.9
4.0
6.7
9.2
12.2
17.6
23.2
28.5
33.5
44.6
Rated output/current
(A) Note 2)
2.8
4.6
7.5
10.6
17.5
24.2
32
46.2
61
74.8
(67.3)
88.0
(79.2)
117.0
(105.3)
Output voltage Note 3)
3-phase 200V to 240V
Rat
ing
Overload current rating
110%-60 seconds, 180%-2 second
Voltage-current
3-phase 200V to 240V - 50/60Hz
Po
w
er
suppl
y
Allowable fluctuation
Voltage + 10%, -15% Note 4), frequency ±5%
Protective method
IP20 Enclosed type (JEM1030)
IP00 Enclosed
type
(JEM1030)
Note 5)
Cooling method
Forced air-cooled
Color
Munsel 5Y-8/0.5
Built-in filter
Basic filter
Item
Specification
Input voltage
3-phase 400V
Applicable motor (kW)
0.4
0.75
1.5
2.2
4.0
5.5
7.5
11
15
18.5
22
30
Type
VFFS1
Form
4004PL 4007PL 4015PL 4022PL 4037PL 4055PL 4075PL 4110PL 4150PL 4185PL 4220PL 4300PL
Capacity (kVA) Note 1)
1.1
1.6
2.8
3.9
6.9
9.1
12.2
17.1
23.2
28.2
33.2
44.6
Rated output current
(A) Note 2)
1.4
2.2
3.7
5.1
9.1
12.0
16.0
22.5
30.5
37.0
(33.3)
43.5
(39.2)
58.5
(52.7)
Rated output voltage
Note 3)
3-phase 380V to 480V
Rat
ing
Overload current rating
110%-60 seconds, 180% -2 second
Voltage-current
3-phase 380V to 480V - 50/60Hz
Po
w
er
suppl
y
Allowable fluctuation
Voltage + 10%, -15%  Note 4), frequency ±5%
Protective method,
IP20 Enclosed type (JEM1030)
IP00 Enclosed
type (JEM1030)
Note 5)
Cooling method
Forced air-cooled
Color
Munsel 5Y-8/0.5
Built-in filter
EMI filter
Note 1: Capacity is calculated at 220V for the 200V models, at 440V for the 400V models.
Note 2: The rated output current in the parenthesis is at 12kHz of PWM carrier frequency (H) setting.
Note 3: Maximum output voltage is the same as the input voltage.
Note 4: ±10% when the inverter is used continuously (load of 100%).
Note 5: Inverter, 22kW or greater, do not have wiring port covers, they have large openings, but there is no space to bend the
external cables inside the unit. If they are fitted external to the cabinet, please use an optional wiring port cover.