E6581381
E-10
5
5.4
Meter setting and adjustment
HOUN
 : Meter selection
HO
 : Meter adjustment
• Function
The signal output from the FM terminal is an analog voltage signal.
For the meter, use either a full-scale 0-1mAdc ammeter or full-scale 0-7.5Vdc (or 10Vdc-1mA) voltmeter.
Switching to 0-20mAdc (4-20mAdc) output current can be made by turning the FM (SW2) slide switch to
the I position. When switching to 4-20mAdc current input, make adjustments using H (analog
output gradient) and H (analog output bias).
[Parameter setting]
Title
Function
Adjustment range
Supposition output at
HOUN
=
Default setting
0: Output frequency
Maximum frequency (HJ)
1: Output current
1.5 times of rated current
2: Set frequency
Maximum frequency (HJ)
3: DC voltage
1.5 times of rated voltage
4: Output voltage command value
1.5 times of rated voltage
5: Input power
1.85 times of rated power
6: Output power
1.85 times of rated power
7: Torque
2.5 times of rated torque
8: Torque current
2.5 times of rated torque
9: Motor cumulative load factor
Rated load factor
10: Inverter cumulative load factor
11: - (Do not select)
Rated load factor
-
12: Frequency setting value (after PID)
Maximum frequency (HJ)
13: VIA Input value
Maximum input value
14: VIB Input value
Maximum input value
15: Fixed output 1 (Output current: 100%)
-
16: Fixed output 2 (Output current: 50%)
-
17: Fixed output 3
(Supposition output at HOUN=17)
-
18: Serial communication data
FA51=1000
HOUN
Meter
selection
19: For adjustments (HOset value is
displayed.)
-
0
HO
Meter
adjustment
-
-
-