Toshiba G9000 用户手册

下载
页码 17
Guide Specification – 3-Phase Static Uninterruptible Power Supply 
 
15 
9.1.2 HTTP Familiarity 
The RemotEye II shall provide a HTTP interface for the UPS to allow easy access of the UPS 
information from any machine with a web browser. At any time, a network workstation or 
management station shall be able to open a RemotEye II website. RemotEye II website shall 
enable the UPS system information to be configured and monitored remotely. RemotEye II 
shall provide access to 3 java applets for monitoring, event logging, and trend analysis. 
 
9.1.3 Shutdown Capability 
The  RemotEye II application software shall allow RemotEye II to remotely notify and 
shutdown selected network servers.  
 
Network Adapter/External Hardware 
   AMD 188ES-20MHz 
   512kB SRAM: 512kB Flash 
   Two asynchronous serial ports 
   10 BaseT RJ-45 connector 
   Toshiba UPS communication protocol 
   SNMP over UDP/IP : HTTP over TCP/IP:ARP, RARP, TFTP and 
ICMP 
   MIB_II  : Toshiba v1.2_MIB :JEM MIB : RFC 1628 
   Traffic LED for network : Status LED for status : Power LED for 
Power 
   2 digit (default setting is Switches 1 and 2 off) 
Temperature Range:  0 – 40  C 
Relative Humidity:  10 – 80 % 
Power Requirements:  12 VDC ungrounded 
                                     2.0 Watts Maximum 
Dimensions: 5.28”(134mm) x 3.40”(86mm) x 1.10”(27mm) (LxWxH) 
Weight:  0.38lbs(170g) 
Certifications:  FCC class A, UL, CUL, CE 
 
 
 
9.2  Remote Status Alarm Panel (RSAP) 
The manufacturer shall optionally provide a RSAP that shall provide a wall-mounted LED mimic 
display for UPS status events of: 
  Input ON 
  Bypass ON 
  Inverter ON 
  Low Battery, AC Fail 
  New alarm annunciation 
  Battery backup for the RSAP monitor.