Guide Specification – 3-Phase Static Uninterruptible Power Supply 
 
 
Harmonic Voltage Distortion  
: < 2% THD (100% Linear Load) 
 
 
 
 
 
 
: < 5% THD (100% Non-linear Load) 
 
Phase Displacement    
 
: 1° Maximum at 100% load 
 
Voltage Transients:  
 
 
100% Load Step Change 
: +/-2% Maximum (Without battery assistance) 
 
 
Loss or Return of Input  
: +/-1% Maximum 
 
 
Transfer from Bypass   to Inverter    : +/-5% Maximum 
 
  
(At Bypass Rated Voltage) 
 
 
Recovery Time 
 
: 1 cycle 
 
 
FUNCTIONAL DESCRIPTION 
 
The UPS shall protect the load against surges, sags, undervoltage, and voltage fluctuation.  The 
UPS shall have built-in protection against permanent damage to itself and the connected load for 
all predictable types of malfunctions. The load shall be automatically transferred to the bypass 
line without interruption in the event of an internal UPS malfunction. The status of protective 
devices shall be indicated on a LCD graphic display screen on the front of the UPS. 
 
5.1  IGBT Rectifier 
5.1.1  General 
A solid-state, multi-level IGBT Rectifier shall convert the incoming AC power into DC 
power to supply the inverter input and system battery.  
 
5.1.2  Voltage Regulation 
The rectifier output voltage shall not deviate by more than +/- 1.0% RMS under the 
following conditions: 
  0% - 100% loading (balanced and unbalanced loading, non-transient) 
  +15% - 20% utility voltage change 
  +/-10.0% utility frequency change 
 
5.1.3  Reflected Harmonic Content 
Input current THD shall be 
  <  3% at 60%-100% load 
  < 6% at 25%-59% load. 
 
5.2  IGBT DC-DC Converter 
 
5.2.1  General 
A solid-state IGBT Battery Converter/Charger shall control battery charging. 
 
5.2.2  Battery Charge Current Limit 
The Converter logic shall provide DC for controlled battery charging. The battery current 
sensing shall be independent of the Converter DC Output current sensing to provide 
precise battery recharging control. The DC/DC Charging Converter shall include a circuit 
to regulate the battery charging current to between 100% and 125%.